7-32
TCPEnding Valid Client Ports - Four 2 byte unsigned integers. These are Ending Client port
for validating TCPconnections.
UDPStarting Valid Client Ports - Four 2 byte unsigned integers. These are Starting Client
ports for validating UDP datagrams.
UDPEnding Valid Client Ports - Four 2 byte unsigned integers. These are Ending Client ports
for validating UDP datagrams
Multicast Group Address- Reserved for future use.
UDPRespond Port - 2 byte unsigned integer. This is UDP port to respond to if UDPresponse
behavior is
77..4499::
CCuussttoommiizzaabbllee
MMooddbbuuss
MMaapp
FFoorrmmaatt
BBlloocckk
((5511220011-5511771122))
QUsing this block, you can customize up to 256 readings. All the readings that are customized in this
block can be seen in the Customized Modbus Map Window Block (12289).
Line Number - 2 bytes.
Point Number - 1 byte.
Reserved - 1 byte. Currently not used.
You can select any Register or Group of Registers that has a Line Number and a Point Number
from the EPM Modbus Register Map. Those selections are used to create a customized grid of up
to 256 readings in the EPM Communicator Device Profile.
Example: In order to read 1 Cycle Phase A-N Voltage as Item Number 1 on your Customized
Modbus Map, you would enter for Item 1: Line Number 10 and Point Number 0.
Refer to GE Communicator User’s Manual for details on the creation of your Customized Modbus
Map.
77..5500::
EEnneerrggyy
SSccaallee
SSeettttiinnggss
((5511771133-5511773388))
QEach register contains 2 bytes. Each byte contains settings for a base quantity. The format of a byte
is as follows:
Digits is a 3 bit field, which is offset by 2 to represent from 2 to 9 displayable digits.
Unit is a 2-bit field, where the values from 0 to 2 represent units of Wh (100), k (103) and M (106).
The value 3 is undefined and is treated the same as 2, signifying M (106).
Decimal Places is a 3-bit field, which represent from 0 to 7 decimal places.
Bit
Meaning Digits Unit Decimal Places
76543210