3.25: Type F25 TOU Profile Monthly End Day

Length: 1 Register (2 bytes)

Each byte stands for a different month of the year. Each byte contains a binary number indicating what the last day of the monthly billing cycle should be for that month. Billing periods are up to and including the end day.

Example:

Register 35507, TOU Calendar Year 1 Monthly End Day Jan & Feb, might contain the following data:

Address

 

35507

Value

 

0E0FH

Bytes

0EH

0FH

Decimal

14

15

Month

Jan

Feb

Day

Jan 14

Feb 15

Meaning

Billing Months run through Jan 14, from Jan

15 through Feb 15 and start on Feb 16

 

3.26: Type F26 TOU Calendar DST Enable / Average Selection

Length: 1 Register (2 bytes)

The first byte contains an enumeration indicating whether Daylight Savings Time is enabled for TOU computations. The enumeration is as follows:

Value (Hex)

Selection

00H

Daylight Savings Time is disabled.

01H

Daylight Savings Time is enabled with default parameters.

02H

Daylight Savings Time is enabled with custom parameters.

The default parameters are to start on the first Sunday in April at 01:59:59.999 and to end on the last Sunday in October at 01:59:59.999. Custom parameters means to use of the dates programmed in the Start and End Date Daylight Savings Time registers from the appropriate TOU Calendar Year.

3-20

Page 238
Image 238
GE EPM 9650/9800 Type F25 TOU Profile Monthly End Day, Type F26 TOU Calendar DST Enable / Average Selection, Decimal Month