3-37
33..5566::
TTyyppee
FF5566
FFlliicckkeerr
CCoouunnttddoowwnnss
QLength: 1 Register (2 bytes)
QRange: 65,535 / 0 seconds
QUnit: 1 second
QThis register contains an unsigned integer which is count-down in seconds until the end of a Flicker
interval, Short Term or Long Term.
Example:
Register 06489, Short Term Flicker Countdown, might contain the following data:
Addr 06489
Value 0400H
Decimal 1024
Interpretation 1024 seconds remain until the next Short Term Flicker is computed.
33..5577::
TTyyppee
FF5577
AAccccuummuullaattiioonn
iinn
tthhee
IInntteerrvvaall
QLength: 1 Register (2 bytes)
QRange: 465,535 / 0
QUnit: VAh, VARh, Wh secondary or pulses
QThese registers contain a 2-byte unsigned integer.
Example:
Register 06397, Total VA hour (Quadrants 1+2+3+4) in the Interval, Secondary, might contain the
following data:
Addr
Value
Decimal
VAh Secondary
06397
0647H
1607
1607 VAh Secondary
33..5588::
TTyyppee
FF5588
1122-bbiitt
RRTTUU
SSaanniittyy
RReeggiisstteerr
QLength: 1 Register
QThis register indicates the status of the meter. Anormally functioning meter reports a value of
0x00000 or 0. Any non-zero value indicates that the unit is operating improperly.