will be used with a single Hookup and the continued use of a Programmable Setting would allow a user to select a Hookup that the meter is not capable of monitoring. The following codes are used to indicate the Form in use:

 

 

EPM Forms

 

 

Code

Form

Wye/Delta

CT’s

PTs

0x000

5S

Delta

2 (recreate Ib)

2

0x001

8S

Delta

3

2

0x002

9S

Wye

3

3

0x003

35S

Delta

2 (recreate Ib)

2

0x004

36S

Wye, 21/2 Element

3

2 (recreate Vbn)

0x005

39S

Wye

4 (In meas)

3

0x006

76S

Wye, 21/2 Element

4 (In meas)

2 (recreate Vbn)

0x007-0x0FF

Undefined,

 

 

 

treated as 5S

 

 

 

 

Banked Executable Option Settings

 

Modbus Register

Setting

9650

9800

65361 High

Form

No

Yes

65361 Low

4 KYZ

No

Yes

65362 High

Com Port 4

No

Yes

65362 Low

Com Port 3

No

Yes

65363 High

Com Port 2

Yes

Yes

65363 Low

Com Port 1

No

Yes

65364 High

1 Amp

Yes

Yes

65364 Low

300 Volt

Yes

Yes

65365 High

Sealing Switch

Yes

Yes

65365 Low

Memory

Yes

Yes

65366 High

Undefined

 

 

65366 Low

Undefined

 

 

65367 High

Undefined

 

 

65367 Low

Undefined

 

 

65368 High

Undefined

 

 

65368 Low

Undefined

 

 

4 KYZ (65361 Low): An option of the Glass Socket (9800) EPM is 4 Internal Dry-contact Relays for Pulse Output, either as KYZ or as End of Interval Pulse. The following codes are used to indi- cate this option: