8-37
will be used with a single Hookup and the continued use of a Programmable Setting would allow a
user to select a Hookup that the meter is not capable of monitoring. The following codes are used to
indicate the Form in use:
4 KYZ (65361 Low): An option of the Glass Socket (9800) EPM is 4 Internal Dry-contact Relays
for Pulse Output, either as KYZ or as End of Interval Pulse. The following codes are used to indi-
cate this option:
Modbus Register Setting 9650 9800
65361 High Form No Yes
65361 Low 4 KYZ No Yes
65362 High Com Port 4 No Yes
65362 Low Com Port 3 No Yes
65363 High Com Port 2 Yes Yes
65363 Low Com Port 1 No Yes
65364 High 1 Amp Yes Yes
65364 Low 300 Volt Yes Yes
65365 High Sealing Switch Yes Yes
65365 Low Memory Yes Yes
65366 High Undefined
65366 Low Undefined
65367 High Undefined
65367 Low Undefined
65368 High Undefined
65368 Low Undefined
Banked Executable Option Settings
Code Form Wye/Delta CT’s PTs
0x000 5S Delta 2 (recreate Ib) 2
0x001 28S Delta 3
0x002 9S Wye 3 3
0x003 35S Delta 2 (recreate Ib) 2
0x004 36S Wye, 21/2 Element 3 2 (recreate Vbn)
0x005 39S Wye 4 (In meas) 3
0x006 76S Wye, 21/2 Element 4 (In meas) 2 (recreate Vbn)
0x007-0x0FF Undefined,
treated as 5S
EPM Forms