Address

Line

Pt

DNP

Description

Range

Units

Type

R/W

 

 

 

Obj

 

 

 

 

 

 

00366

85

0

30

Maximum Thermal Average Phase A Power Factor Quadrant 1

0.999

/ 0

0.001 PF

F8

R

00367

85

1

30

Maximum Thermal Average Phase B Power Factor Quadrant 1

0.999

/ 0

0.001 PF

F8

R

00368

85

2

30

Maximum Thermal Average Phase C Power Factor Quadrant 1

0.999

/ 0

0.001 PF

F8

R

00369

86

0

30

Maximum Thermal Average Power Factor Quadrant 1

0.999

/ 0

0.001 PF

F8

R

00370

87

0

30

Maximum Thermal Average Phase A Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00371

87

1

30

Maximum Thermal Average Phase B Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00372

87

2

30

Maximum Thermal Average Phase C Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00373

88

0

30

Maximum Thermal Average Power Factor Quadrant 2

1.999

/ /1.000

0.001 PF

F8

R

00374

89

0

30

Maximum Thermal Average Phase A Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00375

89

1

30

Maximum Thermal Average Phase B Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00376

89

2

30

Maximum Thermal Average Phase C Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00377

90

0

30

Maximum Thermal Average Power Factor Quadrant 3

2.999

/ 2.000

0.001 PF

F8

R

00378

91

0

30

Maximum Thermal Average Phase A Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00379

91

1

30

Maximum Thermal Average Phase B Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00380

91

2

30

Maximum Thermal Average Phase C Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00381

92

0

30

Maximum Thermal Average Power Factor Quadrant 4

3.999

/ 3.000

0.001 PF

F8

R

00382

93

0

30

Maximum Thermal Average Voltage Imbalance

+327.67% / -327.68%

0.01%

F10

R

00383

93

1

30

Maximum Thermal Average Current Imbalance

+327.67% / -327.68%

0.01%

F10

R

00384

94

0

30

Maximum THD Phase A-N / A-B Voltage

+327.67% / -327.68%

0.01%

F10

R

00385

94

1

30

Maximum THD Phase B-N / B-C Voltage

+327.67% / -327.68%

0.01%

F10

R

00386

94

2

30

Maximum THD Phase C-N / C-A Voltage

+327.67% / -327.68%

0.01%

F10

R

00387

95

0

30

Maximum THD Phase A Current

+327.67% / -327.68%

0.01%

F10

R

00388

95

1

30

Maximum THD Phase B Current

+327.67% / -327.68%

0.01%

F10

R

00389

95

2

30

Maximum THD Phase C Current

+327.67% / -327.68%

0.01%

F10

R

00390

96

0

30

Maximum K-Factor Phase A Current

+327.67% / -327.68%

0.01%

F10

R

00391

96

1

30

Maximum K-Factor Phase B Current

+327.67% / -327.68%

0.01%

F10

R

00392

96

2

30

Maximum K-Factor Phase C Current

+327.67% / -327.68%

0.01%

F10

R

00393-00394

97

0

30

Coincident Thermal Average VAR for Maximum Positive Watt

+32767 VAR / -32768 VAR

1/ 65536 W sec

F7

R

00395-00396

97

1

30

Coincident Thermal Average VAR for Maximum Negative Watt

+32767 VAR / -32768 VAR

1/ 65536 W sec

F7

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Block

 

 

 

 

 

00397-00400

98

0

50

Minimum Block Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

00401-00402

99

0

30

Minimum Thermal Average Phase A-N Voltage

+ 32767 V / 0 V

1/ 65536 V sec

F7

R

00403-00404

99

1

30

Minimum Thermal Average Phase B-N Voltage

+ 32767 V / 0 V

1/ 65536 V sec

F7

R

2- 6

Page 36
Image 36
GE EPM 9650/9800 manual Dnp