7-23
7.35: Custom DNP Definition Block for Binary Input (Object 1) (47425-47456)
Line number: 2-byte unsigned integer
Line number and Point number indicate the Binary Input value used for 8 points in Object 1.
Point number: 1-byte unsigned integer
Class Assignments: 8-bit bitmap (1 byte). Bit 7, 6 and 5 will assign the Binary Input Change
value to a Class. Bit 4 to bit 0 are not used.
Class Assignments for Binary Input Change
Bit 7 Bit 6 Bit 5 Class Assigned
0 0 0 No Class
0 0 1 Class 1
0 1 0 Class 2
0 1 1 Class 3
1 X X No Class
1 X X No Class
1 X X No Class
1 X X No Class
Reserved: 4 bytes. Reserved for future use.
7.36: Custom DNP Definition Block for Binary Output (Object 10) (47457-47458)
Enable / Disable Relays (1-16) (2 bytes): 0: Relay disabled 1: Relay enabled
Bits 1514131211109876543210
Relays 12345678910111213141516
Enable / Disable Resets (17-24) (1 byte): 0: Reset disabled 1: Reset enabled
Bit Resets
15 Log Reset
14 Maximum Reset
13 Minimum Reset
12 Energy Reset
11 Reset Time of Use Current Season and Current Month
10 Manual Waveform Capture
9 Reset KYZ Output Accumulations
8 Reset Unit to Boot Mode - Default Communications Settings
7-0 Reserved