7-8
Transformer Loss Compensation (TLC) Enable - 1 byte, unsigned integer.
Internal KYZ Form - 1 byte bit map.
Refer to the Internal KYZ Settings Block (46330) for more detail.
Abit value of 0 = Form C = Pulse of the relay.
Abit value of 1 = Form A = Transition of the relay.
Daylight Savings Time Start/End.
Address - 4 registers, 8 bytes. Each byte has unsigned integer values (example below).
% Loss of Watt or VAR
Address - 2 registers, 4 bytes, 2 bytes for integers and 2 bytes for fractions.
7.13: Average Settings Block (45949-45952).
Thermal and Block Averaging Time Interval: 1 register, 2 bytes unsigned integer. The unit is in
1 second.
Rolling Average Sub-Interval: 1 register, 2 bytes unsigned integer.
Predictive Rolling Window Average: 1 register, 2 bytes unsigned integer.
Number of Sliding Windows - 1 byte, unsigned integer.
Time of Use Log Enable - currently not used.
7.14: Exception Profile Block (45953-45968).
This block is not yet defined.
Transformer Loss Compensation (TLC) Enable
Value Bit 0 & 1
0 Disabled
1 Iron Only
2 Copper Only
Bit 2
Add
Subtract
3 Both
Internal KYZ Form Relay Assignments
50
Relay Assignments
Bit Number 76 4321
1234LED
Daylight Savings Time Start/End Byte Assignments
Register 4593045929 45931 45932
Byte High Low High Low High
Assignments Reserved Reserved Reserved
LowHighLow
Month Day Hour Minute Second