Transformer Loss Compensation (TLC) Enable - 1 byte, unsigned integer.

Transformer Loss Compensation (TLC) Enable

Value

Bit 0 & 1

Bit 2

0

Disabled

Add

1

Iron Only

Subtract

2

Copper Only

 

3

Both

 

Internal KYZ Form - 1 byte bit map.

Refer to the Internal KYZ Settings Block (46330) for more detail.

A bit value of 0 = Form C = Pulse of the relay.

A bit value of 1 = Form A = Transition of the relay.

 

Internal KYZ Form Relay Assignments

 

 

 

Bit Number

7

6

5

4

3

2

1

0

Relay Assignments

1

2

3

4

LED

 

 

 

Daylight Savings Time Start/End.

Address - 4 registers, 8 bytes. Each byte has unsigned integer values (example below).

 

Daylight Savings Time Start/End Byte Assignments

 

 

Register

45929

45930

45931

45932

Byte

High

Low

High

Low

High

Low

High

Low

Assignments

Reserved

Reserved

Month

Day

Hour

Minute

Second

Reserved

% Loss of Watt or VAR

Address - 2 registers, 4 bytes, 2 bytes for integers and 2 bytes for fractions.

7.13: Average Settings Block (45949-45952).

Thermal and Block Averaging Time Interval: 1 register, 2 bytes unsigned integer. The unit is in 1 second.

Rolling Average Sub-Interval: 1 register, 2 bytes unsigned integer.

Predictive Rolling Window Average: 1 register, 2 bytes unsigned integer.

Number of Sliding Windows - 1 byte, unsigned integer.

Time of Use Log Enable - currently not used.

7.14: Exception Profile Block (45953-45968).

This block is not yet defined.

7-8

Page 328
Image 328
GE EPM 9650/9800 manual Average Settings Block, Exception Profile Block