8.102: Operational Communication Settings Block (65025-65040)

These Registers keep the valid Communication Settings for all four ports. The Communication Settings Block (45057) in the Programmable Settings Block might have the wrong values if they were interrupted while the meter was being updated.

 

 

Operational Communication Settings

 

Value

Protocol

Baud Rate

Parity

Stop Bits Data Bits

Response Delay (ms)

0

Modbus ASCII

4800

None

5

0.00

1

Modbus RTU

9600

Even

6

0.25

2

DNP 3.0

19200

Odd

7

0.50

3

 

38400

Mark

8

0.75

4

 

57600

Space

 

1.00

5

 

115200

 

 

1.25

6

 

 

 

 

1.50

7

 

 

 

1 stop

1.75

8

 

 

 

1.5 stop

2.00

9-14

 

 

 

 

2.25-3.50

15

 

 

 

2 stop

3.75

16-255

 

 

 

 

4.00-63.75

Description: Operational Communication Settings Registers included in this block: Device Address - 2 bytes, unsigned integer, ranging from 0 to 0xFFFF.

Protocol - 1 byte, unsigned integer. Baud Rate - 1 byte, unsigned integer. Parity - 1 byte, unsigned integer. Stop Bits - 1 byte, unsigned integer. Data Bits - 1 byte, unsigned integer. Response Delay - 1 byte, unsigned integer.

8.103: Diagnostic Block (65041-65042)

Description: These registers consist of 32 bits of Data Valid Bits. These registers are created for debugging purposes for GE engineers. When a problem is noticed, GE engineers can use these reg- isters to find the cause of the problem. Customers should NOT use these registers for polling.

8.104: Device Identification Block 2 (65088-65280)

Description: Device Identification Registers included in this block:

196 Xilinx Version / 320 Xilinx Version (65088)

Each number is represented by a 1-byte integer.

8-33

Page 387
Image 387
GE EPM 9650/9800 manual Operational Communication Settings Block, Diagnostic Block, Device Identification Block 2