3.18: Type F18 External Input Accumulations

Length: 2 Registers (4 bytes)

Range: 4,294,967,295/0

Unit: Accumulated Transitions

These registers contain a 4-byte unsigned integer.

Example:

Register 02775-02776, Input Accumulations, Module 1, might contain the following data:

Address

02775

02776

Value

0647H

6164H

4-byte unsigned integer

 

06476164H

Decimal

 

105341284

Accumulated Transitions

105,341,284 Accumulated Transitions

3.19: Type F19 Energy Counter (Packed BCD / Primary)

Length: 4 Registers (8 bytes)

Range: 9,999,999,999,999,999/0 VAh, VARh or Wh primary

1 VAh, VARh or Wh primary

These registers contain 8 bytes of Packed BCD. Each register contains 2 bytes. Each byte contains 2 nibbles. Each nibble represents a decimal digit from 0-9. All together, there are 16 nibbles. Therefore, a 16-digit decimal number can be represented.

Example:

Register 02850-02853, VAhour, might contain the following data:

3-15

Page 233
Image 233
GE EPM 9650/9800 manual Type F18 External Input Accumulations, Type F19 Energy Counter Packed BCD / Primary