EPM Programmable Settings Blocks

The EPM Modbus Register Map can be found in Chapter 2. This chapter gives a detailed description of each of the Programmable Settings Blocks.

7.1: Communication Settings Block (45057-45074)

Device Address - 2 bytes, unsigned integer, ranging from 0000H to FFFFH

Protocol - 1 byte, unsigned integer.

Baud Rate - 1 byte, unsigned integer.

Parity - 1 byte, unsigned integer.

Stop Bits - 1 byte, unsigned integer.

Data Bits - 1 byte, unsigned integer.

Response Delay - 1 byte, unsigned integer.

Port Mode - 1 byte, unsigned integer. The value 1 means Master; value 0 means Slave. Port 1 is always a Slave.

 

Communication Settings Block Specifications

Value

Protocol

Baud Rate

Parity

Stop Bits Data Bits

Response Delay (ms)

0

Modbus ASCII

4800

None

5

0.00

1

Modbus RTU

9600

Even

6

0.25

2

DNP 3.0

19200

Odd

7

0.50

3

 

38400

Mark

8

0.75

4

 

57600

Space

 

1.00

5

 

115200

 

 

1.25

6

 

 

 

 

1.50

7

 

 

 

1 stop

1.75

8

 

 

 

1.5 stop

2.00

9-14

 

 

 

 

2.25-3.50

15

 

 

 

2 stop

3.75

16-255

 

 

 

 

4.00-63.75

7.2: Limit Settings Block (45077-45204)

Limit Comparisons - Internal Representations

An EPM device has 32 Limits Objects.

Each Limit Object performs two independent comparisons with a selected computed value and combines them into a combined output. Information needed to perform these actions: channel identification, comparison values, comparison directions and combination type.