Address

Line

Pt

DNP

Description

Range

Units

Type

R/W

 

 

 

Obj

 

 

 

 

 

 

04919-04920

360

1

30

TOU Current Month Reg 1 Peak Demand Watt (Quadrant 2 + 3)

0 Watt / -32768 Watt

1/ 65536 W sec

F7

R

04921-04922

360

2

30

TOU Current Month Reg 1 Peak Demand VAR (Quadrant 1 + 2)

+32767 VAR / 0 VAR

1/ 65536 VAR sec

F7

R

04923-04924

360

3

30

TOU Current Month Reg 1 Peak Demand VAR (Quadrant 3 + 4)

0 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

04925-04926

361

0

30

TOU Current Month Reg 1 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4)

+32767 VAR/ -32768 VAR

1/ 65536 VAR sec

F7

R

04927-04928

361

1

30

TOU Current Month Reg 1 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3)

+32767 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

04929-04932

362

0

50

TOU Current Month Reg 1 Peak Demand Watt (Q 1 + 4) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

04933-04936

362

1

50

TOU Current Month Reg 1 Peak Demand Watt (Q 2 + 3) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

04937-04940

362

2

50

TOU Current Month Reg 1 Peak Demand VAR (Q 1 + 2) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

04941-04944

362

3

50

TOU Current Month Reg 1 Peak Demand VAR (Q 3 + 4) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time of Use Current Month Reg 2 Block

 

 

 

 

04945-04948

363

0

20

obsolete-TOU Current Month Reg 2 Watthour (Quadrant 1 + 4)

+9,999,999,999,999,999 Wh / 0 Wh

1

WH

F20

R

04949-04952

363

1

20

obsolete-TOU Current Month Reg 2 VAhour (Quadrant 1)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

04953-04956

363

2

20

obsolete-TOU Current Month Reg 2 VARhour (Quadrant 1)

+9,999,999,999,999,999 VARh / 0 VARh

1

VARH

F20

R

04957-04960

363

3

20

obsolete-TOU Current Month Reg 2 VAhour (Quadrant 4)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

04961-04964

363

4

20

obsolete-TOU Current Month Reg 2 VARhour (Quadrant 4)

0 VARh / -9,999,999,999,999,999 VARh

1

VARH

F20

R

04965-04968

363

5

20

obsolete-TOU Current Month Reg 2 Watthour (Quadrant 2 + 3)

0 Wh / -9,999,999,999,999,999 Wh

1

WH

F20

R

04969-04972

363

6

20

obsolete-TOU Current Month Reg 2 VAhour (Quadrant 2)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

04973-04976

363

7

20

obsolete-TOU Current Month Reg 2 VARhour (Quadrant 2)

+9,999,999,999,999,999 VARh / 0 VARh

1

VARH

F20

R

04977-04980

363

8

20

obsolete-TOU Current Month Reg 2 VAhour (Quadrant 3)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

04981-04984

363

9

20

obsolete-TOU Current Month Reg 2 VARhour (Quadrant 3)

0 VARh / -9,999,999,999,999,999 VARh

1

VARH

F20

R

04985-04986

364

0

30

TOU Current Month Reg 2 Peak Demand Watt (Quadrant 1 + 4)

+32767 Watt / 0 Watt

1/ 65536 W sec

F7

R

04987-04988

364

1

30

TOU Current Month Reg 2 Peak Demand Watt (Quadrant 2 + 3)

0 Watt / -32768 Watt

1/ 65536 W sec

F7

R

04989-04990

364

2

30

TOU Current Month Reg 2 Peak Demand VAR (Quadrant 1 + 2)

+32767 VAR / 0 VAR

1/ 65536 VAR sec

F7

R

04991-04992

364

3

30

TOU Current Month Reg 2 Peak Demand VAR (Quadrant 3 + 4)

0 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

04993-04994

365

0

30

TOU Current Month Reg 2 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4)

+32767 VAR/ -32768 VAR

1/ 65536 VAR sec

F7

R

04995-04996

365

1

30

TOU Current Month Reg 2 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3)

+32767 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

04997-05000

366

0

50

TOU Current Month Reg 2 Peak Demand Watt (Q 1 + 4) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

05001-05004

366

1

50

TOU Current Month Reg 2 Peak Demand Watt (Q 2 + 3) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

05005-05008

366

2

50

TOU Current Month Reg 2 Peak Demand VAR (Q 1 + 2) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

05009-05012

366

3

50

TOU Current Month Reg 2 Peak Demand VAR (Q 3 + 4) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time of Use Current Month Reg 3 Block

 

 

 

 

05013-05016

367

0

20

obsolete-TOU Current Month Reg 3 Watthour (Quadrant 1 + 4)

+9,999,999,999,999,999 Wh / 0 Wh

1

WH

F20

R

05017-05020

367

1

20

obsolete-TOU Current Month Reg 3 VAhour (Quadrant 1)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

2- 83

Page 113
Image 113
GE EPM 9650/9800 manual Dnp