3.60: Type F60 Energy Counter

Length: 2 Registers (4 bytes)

Range: +99,999,999 / 0 or 0 / -99,999,999 kWh, kVARh

Unit: 1 kWh, kVARh

Each pair of registers represents an Energy Counter in primary. Each register contains a value from 0 to 9,999 (0x00000 - 0x0270F), representing 4 digits of an Energy Counter. The first register is in units of 10’s of MegaWatthour or Mega VARhour. The second register is in units of kilo Watthour or kilo VARhour. Combined, the pair of registers report up to 100 GWh primary of energy.

Example:

Registers 53267-53268, Positive Watthour, might contain the following data:

Addr

 

53267

 

 

53268

 

Value (Hex)

 

04D2H

 

 

162EH

 

Value (Decimal)

 

1234

 

 

5678

 

Digit

1

2

3

4

5

6

7

8

Unit

G

 

 

M

 

 

k

 

kWh primary

 

 

12,345,678 kWh primary

 

 

3.61: Type F61 12-bit RTU Frequency

Length: 1 Register (2 bytes)

Range: 75 Hz / 45 Hz

Unit: 30 / 4096 Hz

This register contains a 16-bit unsigned integer. The 16-bit integer has been constrained to the bounds of an unsigned 12-bit integer, 4095 to 0. The Frequency represented by this register is offset by 45 Hz.

Example:

Register 53250, Phase A Current, might contain the following data:

Addr

53250

Value

0810H

12-bit Unsigned Integer (Hex)

810H

12-bit Unsigned Integer (Decimal)

+2058

30 /4096 A sec

15.073 Hz

+45 Hz Offset

60.073 Hz