7.32: Miscellaneous DNP Settings Block (47063-47104)

Scale for Analog Output of Average Pulse Accumulation - 1 byte unsigned integer.

Pulse accumulation values are 8-byte. But the Analog Output Module can accept 4-byte quantity. Therefore, only 4 bytes out of 8 bytes will be sent to Analog Output Module. This register decides which 4 bytes will be sent out.

Values

Bytes to be Sent Out

0

Bytes 7,6,5,4

1

Bytes 6,5,4,3

2

Bytes 5,4,3,2

3

Bytes 4,3,2,1

4

Bytes 3,2,1,0

Compressed DNP - 1 byte. Only used in EPM 9450.

Energy in the Interval - 1 byte unsigned Integer. This is the Interval Time for Energy in the Interval. Unit is in minutes. Range is from 60 to 0.

DNP Time Synchronization Enable - 1 byte. Register Address 47064 (Lower Byte).

A value of 1 means that DNP Time Synchronization is enabled

A value of 0 means that DNP Time Synchronization is disabled

DNP Time Synchronization Time Interval - 1 register, 2 bytes. Register Address 47065.

Value

Time (1 Minute Interval)

0

No Time Synchronization

1

1 minute

2

2 minutes

...

...

60

1 hour

61

1 hour, 1 minute

...

 

1439

23 hours, 59 minutes

1440

1 day

1440-65535

1 day (default)

7-19

Page 339
Image 339
GE EPM 9650/9800 manual Miscellaneous DNP Settings Block, Bytes to be Sent Out, Value Time 1 Minute Interval