8-20
The designation “first 128 bytes of the log” is a physical description based on the absolute address-
es of the memory allocated to the log. The first (oldest) record in the log may not be located at the
beginning of the log.
In Time Stamp Modes (0x00001 and 0x00003), the Historical Log 1 Window accesses the Time
Stamps of the records in the Historical Log 1 in blocks of 16 Time Stamps at a time. When the
Index = 0x00000, the Time Stamps of the first 16 records (records 0-15) in the log are readable in
the window; when the Index = 0x00001, the Time Stamps of the second 16 records (records 16-31)
in the log are readable in the window, and so on.
The designation “first 16 records of the log” is a physical description based on the absolute
addresses of the memory allocated to the log. The first (oldest) record in the log may not be locat-
ed at the beginning of the log.
In Paused Modes (0x00000 and 0x00001), the log being accessed is paused and new records are
not added to the log while it is paused.
In Running Modes (0x00002 and 0x00003), the log being accessed is not paused and new records
may be added to the log. When downloading in these modes, it is possible the records may be
overwritten before or during the downloading of records.
Historical Log 2 (38210): When read, this Register returns the Mode in use by the Historical Log
2 Window to access Historical Log 2 on this port. Functionality follows the Historical Log 1
Window Mode (38209).
Limit TriggerLog (38211): When read, this Register returns the Mode in use by the Limit Trigger
Log Window to access Limit Trigger Log on this port. Functionality follows the Historical Log 1
Window Mode (38209).
Limit Snapshot Log (38212): When read, this Register returns the Mode in use by the Limit
Snapshot Log Window to access Limit Snapshot Log on this port. Functionality follows the
Historical Log 1 Window Mode (38209).
Digital Input Log (38213): When read, this Register returns the Mode in use by the Digital Input
Log Window to access Digital Input Log on this port. Functionality follows the Historical Log 1
Window Mode (38209).
Digital Input Snapshot Log (38214): When read, this Register returns the Mode in use by the
Digital Input Snapshot Log Window to access Digital Input Snapshot Log on this port.
Functionality follows the Historical Log 1 Window Mode (38209).
Digital Output Log (38215): When read, this Register returns the Mode in use by the Digital
Output Log Window to access Digital Output Log on this port. Functionality follows the Historical
Log 1 Window Mode (38209).
Digital Output Snapshot Log (38216): When read, this Register returns the Mode used by the
Digital Output Snapshot Log Window to access Digital Output Snapshot Log on this port.