Address

Line

Pt

DNP

Description

Range

Units

Type

R/W

 

 

 

Obj

 

 

 

 

 

45903

 

 

 

Energy Assignement, Relay 3-4, External KYZ Output Module 3

 

 

 

R

45904

 

 

 

Reserved

 

 

 

 

45905

 

 

 

Address, External KYZ Output Module 4

 

 

 

R

45906

 

 

 

Energy Assignement, Relay 1-2, External KYZ Output Module 4

 

 

 

R

45907

 

 

 

Energy Assignement, Relay 3-4, External KYZ Output Module 4

 

 

 

R

45908

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CT & PT Ratio Settings Block

 

 

 

 

45909-45910

 

 

 

Phase Current CT Ratio Numerator

+999,999.99 / +0.01

1/100 A pri

 

R

45911-45912

 

 

 

Phase Current CT Ratio Denominator

+999,999.99 / +0.01

1/100 A sec

 

R

45913-45914

 

 

 

Measured Neutral Current CT Ratio Numerator

+999,999.99 / +0.01

1/100 A pri

 

R

45915-45916

 

 

 

Measured Neutral Current CT Ratio Denominator

+999,999.99 / +0.01

1/100 A sec

 

R

45917-45918

 

 

 

Phase Voltage PT Ratio Numerator

+999,999.99 / +0.01

1/100 V pri

 

R

45919-45920

 

 

 

Phase Voltage PT Ratio Denominator

+999,999.99 / +0.01

1/100 V sec

 

R

45921-45922

 

 

 

Auxiliary Voltage PT Ratio Numerator

+999,999.99 / +0.01

1/100 V pri

 

R

45923-45924

 

 

 

Auxiliary Voltage PT Ration Denominator

+999,999.99 / +0.01

1/100 V sec

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

Hookup and Time Settings Block

 

 

 

 

45925

 

 

 

Hookup

 

 

 

R

45926

 

 

 

Frequency & Time Zone Hour Selection

 

 

 

R

45927

 

 

 

Time Zone Half Hour & Daylight Savings Time Enable

 

 

 

R

45928

 

 

 

Transformer Loss Compensation (TLC) & Internal KYZ Form

 

 

 

R

45929-45932

 

 

 

Daylight Savings Time Start

 

 

 

R

45933-45936

 

 

 

Daylight Savings Time End

 

 

 

R

45937-45938

 

 

 

% Loss of Watts due to Iron (TLC)

 

 

 

R

45939-45940

 

 

 

% Loss of Watts due to Copper (TLC)

 

 

 

R

45941-45942

 

 

 

% Loss of VAR due to Iron (TLC)

 

 

 

R

45943-45944

 

 

 

% Loss of VAR due to Copper (TLC)

 

 

 

R

45945-45948

 

 

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Average Settings Block

 

 

 

 

45949

 

 

 

Thermal and Block Averaging Time Interval

65535 / 0

1 second

 

R

45950

 

 

 

Rolling Averaging Sub-Interval

65535 / 0

1 second

 

R

45951

 

 

 

Predictive Rolling Window Average

100.00 / 0

0.01 %

 

R

45952

 

 

 

Rolling Sub-Intervals / Time of Use Log Enable

1~255/not used

 

 

R

 

 

 

 

 

 

 

 

 

Exception Profile Block

2- 155

Page 185
Image 185
GE EPM 9650/9800 manual Dnp