Address

Line

Pt

DNP

Description

Range

Units

Type

R/W

 

 

 

Obj

 

 

 

 

 

 

03741-03744

291

5

20

obsolete-TOU Prior Month Reg 2 Watthour (Quadrant 2 + 3)

0 Wh / -9,999,999,999,999,999 Wh

1

WH

F20

R

03745-03748

291

6

20

obsolete-TOU Prior Month Reg 2 VAhour (Quadrant 2)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

03749-03752

291

7

20

obsolete-TOU Prior Month Reg 2 VARhour (Quadrant 2)

+9,999,999,999,999,999 VARh / 0 VARh

1

VARH

F20

R

03753-03756

291

8

20

obsolete-TOU Prior Month Reg 2 VAhour (Quadrant 3)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

03757-03760

291

9

20

obsolete-TOU Prior Month Reg 2 VARhour (Quadrant 3)

0 VARh / -9,999,999,999,999,999 VARh

1

VARH

F20

R

03761-03762

292

0

30

TOU Prior Month Reg 2 Peak Demand Watt (Quadrant 1 + 4)

+32767 Watt / 0 Watt

1/ 65536 W sec

F7

R

03763-03764

292

1

30

TOU Prior Month Reg 2 Peak Demand Watt (Quadrant 2 + 3)

0 Watt / -32768 Watt

1/ 65536 W sec

F7

R

03765-03766

292

2

30

TOU Prior Month Reg 2 Peak Demand VAR (Quadrant 1 + 2)

+32767 VAR / 0 VAR

1/ 65536 VAR sec

F7

R

03767-03768

292

3

30

TOU Prior Month Reg 2 Peak Demand VAR (Quadrant 3 + 4)

0 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

03769-03770

293

0

30

TOU Prior Month Reg 2 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4)

+32767 VAR/ -32768 VAR

1/ 65536 VAR sec

F7

R

03771-03772

293

1

30

TOU Prior Month Reg 2 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3)

+32767 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

03773-03776

294

0

50

TOU Prior Month Reg 2 Peak Demand Watt (Q 1 + 4) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

03777-03780

294

1

50

TOU Prior Month Reg 2 Peak Demand Watt (Q 2 + 3) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

03781-03784

294

2

50

TOU Prior Month Reg 2 Peak Demand VAR (Q 1 + 2) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

03785-03788

294

3

50

TOU Prior Month Reg 2 Peak Demand VAR (Q 3 + 4) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Time of Use Prior Month Reg 3 Block

 

 

 

 

03789-03792

295

0

20

obsolete-TOU Prior Month Reg 3 Watthour (Quadrant 1 + 4)

+9,999,999,999,999,999 Wh / 0 Wh

1

WH

F20

R

03793-03796

295

1

20

obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 1)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

03797-03800

295

2

20

obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 1)

+9,999,999,999,999,999 VARh / 0 VARh

1

VARH

F20

R

03801-03804

295

3

20

obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 4)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

03805-03808

295

4

20

obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 4)

0 VARh / -9,999,999,999,999,999 VARh

1

VARH

F20

R

03809-03812

295

5

20

obsolete-TOU Prior Month Reg 3 Watthour (Quadrant 2 + 3)

0 Wh / -9,999,999,999,999,999 Wh

1

WH

F20

R

03813-03816

295

6

20

obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 2)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

03817-03720

295

7

20

obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 2)

+9,999,999,999,999,999 VARh / 0 VARh

1

VARH

F20

R

03821-03824

295

8

20

obsolete-TOU Prior Month Reg 3 VAhour (Quadrant 3)

+9,999,999,999,999,999 VAh / 0 VAh

1

VAH

F20

R

03825-03828

295

9

20

obsolete-TOU Prior Month Reg 3 VARhour (Quadrant 3)

0 VARh / -9,999,999,999,999,999 VARh

1

VARH

F20

R

03829-03830

296

0

30

TOU Prior Month Reg 3 Peak Demand Watt (Quadrant 1 + 4)

+32767 Watt / 0 Watt

1/ 65536 W sec

F7

R

03831-03832

296

1

30

TOU Prior Month Reg 3 Peak Demand Watt (Quadrant 2 + 3)

0 Watt / -32768 Watt

1/ 65536 W sec

F7

R

03833-03834

296

2

30

TOU Prior Month Reg 3 Peak Demand VAR (Quadrant 1 + 2)

+32767 VAR / 0 VAR

1/ 65536 VAR sec

F7

R

03835-03836

296

3

30

TOU Prior Month Reg 3 Peak Demand VAR (Quadrant 3 + 4)

0 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

03837-03838

297

0

30

TOU Prior Month Reg 3 Coin. Dmd. VAR to Peak Dmd. Watt (Q 1 + 4)

+32767 VAR/ -32768 VAR

1/ 65536 VAR sec

F7

R

03839-03840

297

1

30

TOU Prior Month Reg 3 Coin. Dmd. VAR to Peak Dmd. Watt (Q 2 + 3)

+32767 VAR / -32768 VAR

1/ 65536 VAR sec

F7

R

03841-03844

298

0

50

TOU Prior Month Reg 3 Peak Demand Watt (Q 1 + 4) Time Stamp

12/31/9999 23:59:59.99

10 msec

F3

R

2- 72

Page 102
Image 102
GE EPM 9650/9800 manual Dnp