Trane RAUC-C20, RAUC-C50 Service & Maintenance, Compressor Circuit Breaker Data, SS-SVX09A-EN

Models: RAUC-C20 RAUC-C40 RAUC-C25 RAUC-C30 RAUC-C60 RAUC-C50

1 112
Download 112 pages 31.47 Kb
Page 105
Image 105
Service & Maintenance

Service & Maintenance

Table 19. Compressor Circuit Breaker Data

Voltage

Comp

RLA

LRA

Must

Must

 

 

 

 

 

 

 

Tons

 

 

Hold

Trip

 

 

 

 

 

 

200

9

41.4

269.0

50.4

58.0

 

 

 

 

 

 

230

9

41.4

251.0

50.4

58.0

 

 

 

 

 

 

460

9

18.1

117.0

22.0

25.3

 

 

 

 

 

 

575

9

14.4

94.0

17.5

20.2

 

 

 

 

 

 

380/415

9

17.2

110.0

20.9

24.1

 

 

 

 

 

 

200

14

60.5

404.0

73.7

84.7

 

 

 

 

 

 

230

14

60.5

376.0

73.7

84.7

 

 

 

 

 

 

460

14

26.3

178.0

32.0

36.8

 

 

 

 

 

 

575

14

21.0

143.0

25.6

29.4

 

 

 

 

 

 

380/415

14

26.2

174.0

31.9

36.7

 

 

 

 

 

 

Figure 53. Suction Line Filter/Drier Installation

SS-SVX09A-EN

105

Page 105
Image 105
Trane RAUC-C20, RAUC-C50 Service & Maintenance, Compressor Circuit Breaker Data, Suction Line Filter/Drier Installation