System
14.Turn the
15.After shutting the system off, check the compressor oil appearance. Discoloration of the oil indicates that an abnormal condition has occurred. If the oil is dark and smells burnt, it has overheated because of: compressor is operating at extremely high condensing temperatures; high superheat; a compressor mechanical failure; or, occurrence of a motor burnout.
If the oil is black and contains metal flakes, a mechanical failure has occurred. This symptom is often accompanied by a high compressor amperage draw.
If a motor burnout is suspected, use an acid test kit to check the condition of the oil. Test results will indicate an acid level exceeding 0.05 mg KOH/g if a burnout occurred.
Compressor Oil
The scroll compressor uses Trane
Compressor Crankcase Heaters
9 and 10 ton scroll compressors have a
Table 13. Pressure Control Switch Settings
Pressure Switch | Make | Break |
|
|
|
Hi Pressure | 350 psi | 405 psi |
|
|
|
Lo Pressure |
|
|
EVPB | 60 psi | 45 psi |
All others | 40 psi | 30 psi |
| ||
|
|
|
Condenser Fan Cycling switch | 275 psi | 155 psi |
|
|
|
(EVP only w/HGB - wo/HGB) std. |
|
|
Lo Ambient Thermostat | 33 F | 30 F |
|
|
|
Compressor Winding | 181F | 221 F |
Note: Pack Stock units will have both low pressure switches shipped and the user should use the above valves that apply
Table 14. Recommended Refrigerant Capacities
|
|
| Total Interconnecting Line Length |
|
Capacity |
| 50 | 100 | 150 |
|
|
|
| |
| Approximate Total System Refrigerant Charge (Lbs. Per Circuit) |
|
20Ton
25Ton
30Ton
40Ton
50Ton
60Ton
49 | 56 | 64 |
58 | 73 | 87 |
71 | 85 | 99 |
46 | 53 | 61 |
56 | 70 | 85 |
68 | 82 | 97 |
Table 15. Minimum starting Ambient Temperature
Minimum Starting Ambient (1)
Standard Units | Low Ambient Units |
|
|
93 |