Refrigerant Piping

Installation

Refrigerant Piping

Refrigerant piping must be properly sized and applied. These two factors have a very significant effect on both system performance and reliability.

NOTICE

Use Type “L” refrigerant grade copper tubing only.

Refrigerant Piping should be sized and laid out according to the job plans and specifications. This should be done when the system components are selected.

Suction Line Piping

Proper suction line sizing is required to guarantee that oil is returned to the compressor throughout the operating system. Furthermore, the line must be sized so that the pressure drop does not excessively affect capacity or efficiency. To accomplish both, it may be necessary to have two sizes, one for horizontal run and vertical drops, and another for the vertical lifts. The suction line size pre- selected in the Table below are independent of the line length for a properly charged RAUC unit operating in a normal air conditioning application.

For more information, refer to the latest edition of Application Guide SS-APG001-EN.

1.Do not use suction line traps.

2.Do not use double risers.

3.Avoid putting liquid lines underground.

4.Route suction lines as short and direct as possible.

5.Slope suction lines toward the evaporator ¼-inch to 1-inch for every 10 feet.

6.Insulate the suction lines.

7.The suction line filter should be as close to the compressor as possible.

Note: If Suction Riser Exceeds 50 Feet, Trane Must Review The Application.

Suction Line Interconnecting Tubing

 

 

OD Vertical

Capacity

OD Horizontal (Per Circuit)

(Per Circuit)

 

 

 

20 Ton

2-1/8"

1- 5/8"

 

 

 

25 Ton

2-1/8"

1-5/8"

 

 

 

30 Ton

2-1/8"

2-1/8"

 

 

 

40 Ton

2-1/8"

1-5/8"

 

 

 

50 Ton

2-1/8"

2-1/8"

 

 

 

60 Ton

2-1/8"

2-1/8"

Note: If risers exceed 50 feet, the application must be reviewed by Trane.