Trane RAUC-C40, RAUC-C50, RAUC-C30 manual Economizer Actuator Circuit, Installation, DC Conductors

Models: RAUC-C20 RAUC-C40 RAUC-C25 RAUC-C30 RAUC-C60 RAUC-C50

1 112
Download 112 pages 31.47 Kb
Page 52
Image 52
Table 10. DC Conductors

Installation

These components may include:

Field installed Discharge Duct Sensor (6RT1 CV units);

Field installed Return Duct Sensor (6RT6 CV units);

Field installed Discharge Air Sensor (6RT3 VAV units);

Field installed Chilled Water Sensor (6RT2 EVP units);

1.Wiring for the components utilizing a DC analog input\output signal must be shielded cable (Belden 8760 or equivalent). Ground the shield at one end only.

2.Table 10 lists the conductor sizing guidelines that must be followed when interconnecting a DC binary output device to the unit.

Note: Resistance in excess of 2.5 ohms per conductor can cause deviations in the accuracy of the controls.

3.Ensure that the wiring between the binary controls and the unit’s termination point does not exceed two and a half (2.5) ohms/conductor for the length of the run.

4.Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires.

Table 10. DC Conductors

Distance from Unit to Control

Recommended Wire Size

 

 

000 - 499 feet

16 gauge

 

 

500 - 1000feet

14 gauge

 

 

Economizer Actuator Circuit

Each unit ordered with the Constant Volume or Variable Air Volume control option has the capability of controlling a field installed economizer. The diagram below illustrates a typical economizer actuator circuit.

When connecting the economizer actuator control circuit to the terminal board inside the unit control panel, refer to the actual unit wiring diagram for terminal designation, i.e. W, B, R, & Y. A separate power supply for the actuator(s) must be field provided.

52

SS-SVX09A-EN

Page 52
Image 52
Trane RAUC-C40, RAUC-C50, RAUC-C30, RAUC-C60, RAUC-C20, RAUC-C25 manual Economizer Actuator Circuit, Installation, DC Conductors