Image 22
Table 1.

Installation

 

 

 

Table 1.

Typical Unit Weights & Point Loading Data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

 

 

 

 

 

Unit Weight on Isolator @ Mounting Location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

Weight

 

Location 1

2

 

 

3

4

 

 

5

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

AL

CU

 

AL

CU

AL

 

CU

AL

 

CU

AL

 

CU

AL

 

CU

AL

 

CU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C20

1522

1720

 

509

559

398

 

439

345

 

404

270

 

317

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C25

1640

1842

 

555

602

421

 

467

378

 

436

286

 

338

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C30

1824

2115

 

580

640

635

 

708

291

 

364

318

 

403

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C40

2769

3102

 

480

523

457

 

501

473

 

528

450

 

506

466

 

533

443

 

511

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C50

3148

3540

 

586

643

562

 

620

536

 

601

514

 

579

485

 

559

465

 

538

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C60

3480

4050

 

640

722

618

 

703

590

 

684

570

 

666

540

 

646

522

 

629

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Mounting locations correlate with those shown in point loading illustration

Table 2. Typical EVP Chiller Weights & General Data

Chiller

Shipping

Operating

Number of

Water Volume in

Refrigerant Charge

 

Size

Weight2

Weight

Ref. Ckts.

Gallons3

in Lbs.4

 

20 Ton

80

100

1

2.0

2.5

 

 

 

 

 

 

 

 

 

 

25 Ton

92

116

1

2.4

3.0

 

 

 

 

 

 

 

 

 

 

30 Ton

105

133

1

2.9

3.7

 

 

 

 

 

 

 

 

 

 

40 Ton

152

186

2

3.7

4.7

 

 

 

 

 

 

 

 

 

 

50 Ton

170

211

2

4.3

5.5

 

 

 

 

 

 

 

 

 

 

60 Ton

242

309

2

7.0

8.9

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

2 - Shipping and Operating weights are approximate

 

 

 

 

 

3 - Includes volume of Water Piping Kit.

 

 

 

 

 

4 - Refrigerant charge is approximate for chiller evaporator only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shipping

 

 

Location of Center of Gravity

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

Z

 

 

weight (Max.

 

 

 

 

 

 

 

 

 

 

 

Unit Size

Lbs)

 

In

mm

 

In

mm

 

 

 

 

 

 

 

 

 

 

C20

1724

 

38-1/16

968

 

26-3/8

671

 

 

 

 

 

 

 

 

 

 

C25

1843

 

38-1/16

968

 

26-3/16

666

 

 

 

 

 

 

 

 

 

 

C30

2107

 

34-1/16

865

 

31-1/2

800

 

 

 

 

 

 

 

 

 

 

C40

3088

 

44-3/16

1122

 

43-1/16

1095

 

 

 

 

 

 

 

 

 

 

C50

3532

 

54-11/16

1389

 

43-3/16

1097

 

 

 

 

 

 

 

 

 

 

C60

4024

 

55-3/16

1402

 

43-3/8

1102

 

 

 

 

 

 

 

 

 

 

22

SS-SVX09A-EN