Trane RAUC-C40 manual System Start-Up, Minimum starting Ambient Temperature, Compressor Sequence

Models: RAUC-C20 RAUC-C40 RAUC-C25 RAUC-C30 RAUC-C60 RAUC-C50

1 112
Download 112 pages 31.47 Kb
Page 94
Image 94
Table 16. Compressor Sequence

System Start-Up

Table 15. Minimum starting Ambient Temperature

Unit

With

No

With

No

Size

HGBP

HGBP

HGBP

HGBP

 

 

 

 

 

20-60

45°

40°

10°

Note: Minimum starting ambients in degrees F and is based on the unit operating at minimum step of unloading and 5 mph wind across condenser.

Table 16. Compressor Sequence

Unit Size

Control Step

Circuit 1

Circuit 2

 

 

 

 

1

A

50%

 

20

A, B

100%

 

2

 

 

 

 

 

1

B

40%

 

25

A, B

100%

 

2

 

 

 

 

 

1

A

50%

 

30

A, B

100%

 

2

 

 

 

 

 

1

A

50%

 

2

A

50%

C (50%)

40

A

50%

C, D (100%)

3

4

A, B

100%

C, D (100%)

 

 

 

 

1

A

61%

 

2

A

61%

C (61%)

50

A

61%

C, D (100%)

3

4

A, B

100%

C, D (100%)

 

 

 

 

1

A

50%

 

2

A

50%

C (50%)

60

A

50%

C, D (100%)

3

4

A, B

100%

C, D (100%)

Note: A, B, C and D indicate which compressor in the unit is operating. (%) indicates the amount of the circuit in operation during a given step. refer to the compressor location illustration for the unit.

94

SS-SVX09A-EN

Page 94