Trane RAUC-C20 Controls using 24 VAC, Controls using DC Analog Input/Outputs, Hazardous Voltage

Models: RAUC-C20 RAUC-C40 RAUC-C25 RAUC-C30 RAUC-C60 RAUC-C50

1 112
Download 112 pages 31.47 Kb
Page 51
Image 51
Controls using 24 VAC

Installation

Controls using 24 VAC

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Before installing any connecting wiring, refer to Figure 3 to Figure 8 for the electrical access locations provided on the unit and Table 9 for AC conductor sizing guidelines, and;

1.Use copper conductors unless otherwise specified.

2.Ensure that the AC control wiring between the controls and the unit’s termination point does not exceed three (3) ohms/conductor for the length of the run.

NOTICE

Resistance in excess of 3 ohms per conductor may cause component failure due to insufficient AC voltage supply.

3.Be sure to check all loads and conductors for grounds, shorts, and miswiring.

4.Do not run the AC low voltage wiring in the same conduit with the high voltage power wiring. Typical Low voltage components may include:

zone thermostat wiring (AC & DC wiring); system control switch wiring (VAV units); night setback relay wiring (VAV units); economizer actuator circuit wiring (VAV units); discharge air sensor wiring (VAV units); chilled water temperature sensor (EVP units); jumpers for hot gas bypass operation.

Table 9. AC Conductors

Distance from

Recommended

Unit to Control

Wire Size

 

 

000 - 460 feet

18 gauge

 

 

461 - 732 feet

16 gauge

 

 

733 - 1000 feet

14 gauge

 

 

Controls using DC Analog Input/Outputs

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

Before installing any connecting wiring between the unit and components utilizing a DC analog input\output signal, refer to Figure 3 to Figure 8 for the electrical access locations provided on the unit.

SS-SVX09A-EN

51

Page 51
Image 51
Trane RAUC-C20 Controls using 24 VAC, Controls using DC Analog Input/Outputs, Hazardous Voltage, Notice, Installation