System
Final System Setup
After completing the
[ ] Turn the 115 volt control circuit switch 1S2 “Off”.
[ ] Program the Night Setback (NSB) panel (if applicable) for proper unoccupied operation. Refer to the programming instructions for the specific panel.
[ ] Verify that the “System” selection switch and the “Fan Mode” selection switch at the Remote panel is set correctly.
[ ] Verify that the “System” control switch for the supply fan or the chilled water pump is “On”.
[ ] Set the correct “Operating Temperature” for the system at the system controller. Refer to Figure 17 for the recommended control set points for the appropriate control option.
[ ] Turn the 115 volt control circuit switch 1S2 “On”. The system will start automatically once a request for cooling has been given.
[ ] Verify that all exterior panels and the control panel doors are secured in place.
Table 17. Recommended Operating Setpoints
Control |
| Control Setting | Recommended Setting |
|
|
|
|
|
| Supply Air Setpoint | Set at design discharge (supply) air temperature; |
|
| minimum setting = 55o F | |
|
|
| |
Discharge Air |
|
|
|
Controller |
|
| Set at maximum amount of allowable reset for supply |
(VAV units only) |
| Reset Setpoint | |
| air setpoint. | ||
|
|
| |
|
|
|
|
|
| Control Band | Set at 6o F Minimum Setpoint |
|
|
|
|
|
| Leaving Fluid Setpoint | Set at design leaving chilled water temperature |
|
| (typically) 44o F | |
|
|
| |
|
|
|
|
Chiller Control |
| Reset Setpoint | Set at maximum amount of allowable reset for |
(EVP units only) |
| leaving fluid setpoint. | |
|
| ||
|
|
| |
Freezestat |
|
|
|
|
|
|
|
|
| Control Band | Set at 6o F Minimum Setpoint |
|
| Low Limit Solution Temperature | Set at 5o F Minimum above the Chilled Solution |
|
| Freeze Temperature | |
|
|
| |
|
|
| |
Zone Thermostat (CV units | Zone Setpoint | Set at desired space temperature. | |
only) |
| ||
|
|
| |
|
|
| |
Note: "No Controls" Units | See System Engineer |
|
102 |