Figure 43. Condenser Fan Locations
Low Ambient Dampers
Low Ambient Dampers are available as a factory installed option or can be
The low ambient damper actuator controls damper modulation for each refrigerant circuit in response to saturated condensing temperature.
Compressor Crankcase Heaters
Each compressor is equipped with a crankcase heater and is controlled by a 600 volt auxiliary switch on the compressor contactor. The proper operation of the crankcase heater is important to maintain an elevated compressor oil temperature during the “Off” cycle to reduce oil foaming during compressor starts.
When the compressor starts, the sudden reduction in crankcase pressure causes the liquid refrigerant to boil rapidly causing the oil to foam. This condition could damage compressor bearings due to reduced lubrication and could cause compressor mechanical failures.
When power has been “Off” for an extended period, allow the crankcase heater to operate a minimum of 8 hours before starting the unit.
Pump Down
Each circuit will go into a pump down cycle when the last compressor on that circuit is turned "Off". During pump down, the solenoid valves are closed, the reset circuit is bypassed and the compressor will continue to run until the 30 psig pressure switch opens.