17 – Wiring (continued)

7-7 AC Input/Output Wiring (Single UPS)

1 After de-energizing all input and output (AC and DC) of the UPS 2 system, remove the terminal block cover from the UPS system.

3

4 2 If you did not connect the ground cable in Section 7-6, connect the UPS system’s grounding terminal A to your facility’s earth ground

Bwith a 4 AWG (5.189 mm) ground cable. Keep the ground cable connected at all times after installation.

5

6

 

 

3

Remove the UPS system’s front bezel to expose the circuit

 

 

 

 

breakers. First, confirm that the main input circuit breaker switch

7

 

 

 

Q1

and the bypass input circuit breaker switch

Q2

are both off.

 

 

 

Second, confirm that the manual bypass circuit breaker switch

 

 

 

 

 

Q3

 

 

 

 

is off. Third, confirm that the output circuit breaker switch

 

is

 

 

 

 

Q4

 

 

 

 

off.

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Confirm the phase of each cable, then connect the cables according

 

 

 

 

 

4

9

 

 

 

to the UPS system terminal block diagram in Section 7-3. See

 

 

 

Section 7-5for cable size requirements. Cabling should be

 

 

 

 

protected by flexible conduit and routed through the appropriate

 

 

 

 

knockouts in the terminal block cover. Warning: Observe proper

 

 

 

 

 

phase rotation by connecting R to R, S to S, T to T and N to N.

10

 

 

 

Failure to observe proper phase will damage the UPS system

 

 

 

and create a risk of personal injury and property damage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

Replace the UPS system’s terminal block cover.

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

B

A

2

Q4

 

Q3

 

Q2

 

Q1

 

 

 

 

 

 

 

 

 

 

 

3

 

R S T N R S T N

R S T N

4

 

5

20

Page 20
Image 20
Tripp Lite SU40KX, SU80KX AC Input/Output Wiring Single UPS, Failure to observe proper phase will damage the UPS system