16 – Internal Battery Connection (continued)

6-2 Internal Battery Connection Procedure (continued)

6 Slide a battery string with a red cable into an empty slot within 2 the battery compartment. Make sure the battery string is oriented

as shown in the diagram. Note: Start with the empty slots at the bottom of the battery compartment and work toward the empty slots at the top of the battery compartment.

3

4

7 Slide a battery string with a black cable into an empty slot within the battery compartment, next to the battery string that you inserted

5 in step 6. Make sure the battery string is oriented as shown in the diagram. Repeat steps 6 and 7 as needed until all the battery strings have been inserted into the empty battery slots. Note: Depending on the model of the UPS system, some battery compartment slots

TERMINALS

SIDE VIEW

6

TERMINALS

6

7

may remain empty.

SIDE VIEW

7

8 Reconnect the fuse block bracket. (The letters on the fuse block bracket should be upright when it is in the correct orientation.)

8

9

8

 

 

 

 

Connect the blue and white jumper cables on each internal battery

10

 

9

 

 

 

pack to the corresponding fuse block. The labeling next to the fuse

 

 

 

 

block identifies the correct fuse block for each cable.

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

 

Insert the battery cartridge fuses into each fuse block. The fuses are

 

10

 

 

 

 

interchangeable. Make sure the fuses are firmly snapped into place.

 

 

 

 

Warning: Battery cartridge fuses must be inserted last due to

 

 

 

 

 

 

 

 

potential arcing of connectors. Blown fuses must be replaced

13

 

 

 

by a qualified electrician. Replace only with fuses of the same

 

 

 

type and rating.

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

9

10

14

Page 14