Tripp Lite SU20KX Battery Setup, Display and Configuration continued, Output Setup continued

Models: SU40KX SU20KX SU80KX

1 60
Download 60 pages 3.02 Kb
Page 43
Image 43
6Redundancy

10 – Display and Configuration (continued)

10-5-2 Output Setup (continued)

5From the “FREQ CONVERTER MODE” screen, use the scroll buttons (10-5-3 Battery Setup,Manual background) to select the desired setting and press the enter button (Manual background) to confirm the setting. In frequency converter mode, the UPS will convert the incoming electrical power frequency to a different output frequency. Therefore, 60Hz can change to 50Hz output or 50Hz input can change to 60Hz output. When in frequency converter mode, bypass power is not an available source (the UPS will not transfer to bypass).

5

6Redundancy

Use “Manual background” or ”Manual background” to select the desired number of modules for redundancy (usually one) for redundancy, then press ”Manual background ” to confirm.

This feature allows the user to determine an acceptable power output limit to guarantee a redundancy of N+1. When this feature is enabled, the UPS will send an alarm when power usage exceeds 80% of the “non-redundant” power modules while maintaining the number of redundant power modules set. For example, on an 80kVA UPS, if a Redundancy Setup is set to “1 Power Module”, the UPS will trigger an alarm when you exceed 80% of 60kVA as to guarantee one power module for N+1 redundancy.

Press “ESC” to return to the “UPS SETUP” menu.

6

10-5-3 Battery Setup

Use “Manual background” or ”Manual background” to select “BATTERY”, then press ”Manual background ” to confirm.

All parameters in this segment can only be changed when UPS is in “Bypass Mode”.

43

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Page 43
Image 43
Tripp Lite SU20KX, SU80KX, SU40KX Battery Setup, Display and Configuration continued, Output Setup continued, Redundancy