9 – |
| 1 |
|
| |
|
| |
|
|
|
| ||
Warning: When the UPS system is in manual bypass, the inverter shuts down. Connected equipment loads are powered by the bypass | 2 | |
(reserve) power source and will not receive battery backup during a utility power failure. |
•1 For the first UPS system you wish to shut down, press the OFF |
|
|
|
|
|
| |
| button A for 3 seconds (until you hear a beep), then release |
|
|
|
|
|
|
| the button. If the other UPS system can support the connected |
|
|
|
|
|
|
| equipment loads alone, the UPS system that was turned off will |
|
|
|
|
| 3 |
| shut down its inverter and its LCD screen will read “LOAD NOT |
|
|
|
|
| |
|
|
|
|
|
|
| |
| POWERED”. The other UPS system’s LCD screen will read |
|
|
|
|
|
|
| “ONLINE MODE”. If the total connected equipment load is too |
|
|
|
|
|
|
| large to be handled by a single UPS system, both UPS systems |
|
|
|
| A |
|
| will shut down their inverters and switch to bypass mode, and their | 1 |
|
|
| 4 | |
|
|
|
|
| |||
| LCD screens will read “ON AUTO BYPASS”. Repeat step 1 for |
|
|
|
|
|
|
| the second UPS system you wish to shut down. |
|
|
|
|
|
|
•2 | Switch off the main input circuit breaker switch Q1 of each UPS |
|
|
|
|
|
|
| system. |
|
|
|
| Q1 | 5 |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| Output | Manual | Bypass | Main |
|
|
| 2 |
| Bypass | Input | Input | 6 |
|
|
|
|
|
| ||
•3 | Confirm that both UPS systems are shut down, then switch on |
|
|
|
|
| |
|
|
|
|
|
| ||
| the manual bypass input circuit breaker switch Q3 of each UPS |
|
|
|
|
|
|
| system. The bypass (reserve) power source will power the loads |
|
|
|
|
|
|
| and the LCD screen will read “ON MANUAL BYPASS”. |
|
| Q3 |
|
| 7 |
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
|
|
| Output | Manual | Bypass | Main |
|
|
| 3 |
| Bypass | Input | Input | 8 |
|
|
|
|
|
| ||
•4 | Switch off the bypass input circuit breaker switch Q2 and the |
|
|
|
|
| |
| output circuit breaker switch Q4 of each UPS system. The LCD |
|
|
|
|
|
|
| screen will turn off completely. |
|
|
|
|
|
|
|
|
| Q4 |
| Q2 |
| 9 |
|
|
|
|
|
|
| |
|
|
| Output | Manual | Bypass | Main |
|
|
| 4 |
| Bypass | Input | Input |
|
|
|
|
|
|
| 10 | |
•5 If the UPS systems have external battery cabinets connected, |
|
|
|
|
| ||
| switch off the external battery cabinet circuit breaker switch A |
|
| A |
|
|
|
| of each battery pack. On the SU20KX or SU40KX, turn OFF the |
|
|
|
|
| |
| battery breaker on the back of the UPS. |
|
|
|
|
|
|
|
|
|
|
|
|
| 11 |
|
| 5 |
|
|
|
|
|
•6 | In this mode, only the manual bypass path (including the manual |
|
|
|
|
| 12 |
| bypass circuit breaker Q3 ), the load terminals of the output |
|
|
|
|
|
|
| circuit breaker switch Q4 and the terminal block B contain |
|
|
|
| B |
|
| hazardous voltage, allowing qualified service personnel to perform |
|
|
|
|
| |
| Q4 | Q3 |
|
|
|
| |
| maintenance or repair. Note: Qualified service personnel may |
|
|
|
| ||
|
|
|
|
|
| 13 | |
| prefer to |
|
|
|
|
| |
| local codes and the nature of the maintenance or repair. |
|
|
|
|
|
|
|
| 6 |
|
|
|
|
|
|
|
|
|
|
|
| 14 |
|
| 31 |
|
|
|
|
|