Tripp Lite SU20KX Start-Up, Shutdown and Bypass continued, Manual Bypass Procedure Parallel UPS

Models: SU40KX SU20KX SU80KX

1 60
Download 60 pages 3.02 Kb
Page 31
Image 31
9-10 Manual Bypass Procedure (Parallel UPS)

9 – Start-Up, Shutdown and Bypass (continued)

 

1

 

 

 

 

9-10 Manual Bypass Procedure (Parallel UPS)

 

 

 

Warning: When the UPS system is in manual bypass, the inverter shuts down. Connected equipment loads are powered by the bypass

2

(reserve) power source and will not receive battery backup during a utility power failure.

1 For the first UPS system you wish to shut down, press the OFF

 

 

 

 

 

 

 

button A for 3 seconds (until you hear a beep), then release

 

 

 

 

 

 

 

the button. If the other UPS system can support the connected

 

 

 

 

 

 

 

equipment loads alone, the UPS system that was turned off will

 

 

 

 

 

3

 

shut down its inverter and its LCD screen will read “LOAD NOT

 

 

 

 

 

 

 

 

 

 

 

 

 

POWERED”. The other UPS system’s LCD screen will read

 

 

 

 

 

 

 

“ONLINE MODE”. If the total connected equipment load is too

 

 

 

 

 

 

 

large to be handled by a single UPS system, both UPS systems

 

 

 

 

A

 

 

will shut down their inverters and switch to bypass mode, and their

1

 

 

 

4

 

 

 

 

 

 

LCD screens will read “ON AUTO BYPASS”. Repeat step 1 for

 

 

 

 

 

 

 

the second UPS system you wish to shut down.

 

 

 

 

 

 

2

Switch off the main input circuit breaker switch Q1 of each UPS

 

 

 

 

 

 

 

system.

 

 

 

 

Q1

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Manual

Bypass

Main

 

 

 

2

 

Bypass

Input

Input

6

 

 

 

 

 

 

3

Confirm that both UPS systems are shut down, then switch on

 

 

 

 

 

 

 

 

 

 

 

 

the manual bypass input circuit breaker switch Q3 of each UPS

 

 

 

 

 

 

 

system. The bypass (reserve) power source will power the loads

 

 

 

 

 

 

 

and the LCD screen will read “ON MANUAL BYPASS”.

 

 

Q3

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

Manual

Bypass

Main

 

 

 

3

 

Bypass

Input

Input

8

 

 

 

 

 

 

4

Switch off the bypass input circuit breaker switch Q2 and the

 

 

 

 

 

 

output circuit breaker switch Q4 of each UPS system. The LCD

 

 

 

 

 

 

 

screen will turn off completely.

 

 

 

 

 

 

 

 

 

Q4

 

Q2

 

9

 

 

 

 

 

 

 

 

 

 

Output

Manual

Bypass

Main

 

 

 

4

 

Bypass

Input

Input

 

 

 

 

 

 

 

10

5 If the UPS systems have external battery cabinets connected,

 

 

 

 

 

 

switch off the external battery cabinet circuit breaker switch A

 

 

A

 

 

 

 

of each battery pack. On the SU20KX or SU40KX, turn OFF the

 

 

 

 

 

 

battery breaker on the back of the UPS.

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

5

 

 

 

 

 

6

In this mode, only the manual bypass path (including the manual

 

 

 

 

 

12

 

bypass circuit breaker Q3 ), the load terminals of the output

 

 

 

 

 

 

 

circuit breaker switch Q4 and the terminal block B contain

 

 

 

 

B

 

 

hazardous voltage, allowing qualified service personnel to perform

 

 

 

 

 

 

Q4

Q3

 

 

 

 

 

maintenance or repair. Note: Qualified service personnel may

 

 

 

 

 

 

 

 

 

 

13

 

prefer to de-energize the UPS systems completely, depending on

 

 

 

 

 

 

local codes and the nature of the maintenance or repair.

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

31

 

 

 

 

 

Page 31
Image 31
Tripp Lite SU20KX, SU80KX, SU40KX owner manual Start-Up, Shutdown and Bypass continued, Manual Bypass Procedure Parallel UPS