6 – Internal Battery Connection (continued)
1
6-2 Internal Battery Connection Procedure
•1 Place the UPS system in bypass (or turn it completely off) and turn off the internal battery circuit breaker switch, located on the rear of the UPS system.
•2 Remove the battery access bezels, located on the front of the UPS system.
•3 Remove the battery cartridge fuses from each fuse block.
•4 Disconnect the blue and white jumper cables attached to each fuse
block. Warning: When disconnecting the jumper cables, pull them straight away from the fuse block with even force. Do not wiggle them
•5 Remove the fuse block bracket. Note its orientation before removal.
| 2 |
| 3 |
1 | 4 |
|
5
6
2
7
8
3 |
9 |
10 |
11 |
4 |
12 |
13 |
5 |
14 |
13