Warning: The UPS system’s output voltage is set at 220/380V by default. If you require output voltage of 230/400V or 240/415V, you must | |||
| |||
| |||
change the UPS system’s output voltage by accessing the output setup menu described in Section |
| ||
bypass mode before changing the output voltage. Do not connect your equipment to the UPS system’s output until you have set the proper | 2 | ||
parameters. | |||
|
|
|
9-1 Control Panel and Breaker Diagrams
•A “NORMAL” LED
•B “BATTERY” LED
•C “BYPASS” LED
•D “FAULT” LED
•E LCD Status Screen
•F “ESC” (Escape) Button
•G Scroll Buttons ( and )
•H Enter Button ( )
•I ON Button
•J OFF Button
•K “EPO” (Emergency Power Off) Button
Q1 Main Input Circuit Breaker Switch
Q2 Bypass Input Circuit Breaker Switch
Q3 Manual Bypass Circuit Breaker Switch
Q4 Output Circuit Breaker Switch
| E | F | I | K | 3 |
A |
|
|
|
|
|
B |
| G |
|
|
|
C |
|
|
|
| |
|
|
|
| 4 | |
D |
|
|
|
| |
|
|
|
|
| |
1 |
| H | J |
|
|
|
|
|
|
| |
| Control Panel |
|
| 5 | |
|
|
|
|
| |
Q4 | Q3 | Q2 |
| Q1 | 6 |
|
|
|
|
| |
Output | Manual | Bypass |
| Main |
|
2 | Bypass | Input |
| Input |
|
Circuit Breaker Switches (UPS System Front Panel) | 7 |
9-2 Preliminary Checklist (Single UPS)
•All circuit breaker switches should be off, including the breaker of the external battery cabinet (if present).
•Confirm that no voltage potential exists between Neutral and Ground.
•Confirm that the input power source matches the rating (voltage, frequency and phase) of the UPS system.
Note: After
9-3 Standard Start-Up Procedure (Single UPS)
•1 If there is an external battery cabinet connected, switch on the circuit breaker A of the external battery cabinet. On the SU20KX or SU40KX, turn on the battery breaker on the back of the UPS.
A
1
8
9
10
11
12
•2 Confirm that the manual bypass circuit breaker switch Q3 is off.
25
Q3
Output | Manual | Bypass | Main |
2 | Bypass | Input | Input |
|
|
|