Tyco 4100U installation manual SPS Auxiliary Power Wiring, Continued, 4.Auxiliary Power Wiring

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 117
Image 117
SPS Auxiliary Power Wiring, Continued

SPS Auxiliary Power Wiring, Continued

Wiring

The SPS can connect to auxiliary power appliances via the dedicated auxiliary power tap

 

(TB3). If more power is needed, any of the three NAC outputs can be used for EMC

 

auxiliary power.

 

 

AUXILIARY

AUXILIARY

AUXILIARY

 

POWER

POWER

POWER

0.75 mm2 to 4 mm2

 

 

TB2

B+ B- A+ A- B+ B- A+ A- B+ B- A+ A-

 

 

NAC points must be

 

 

reconfigured as

 

 

auxiliary power

 

 

output points in the

 

 

programmer

Dedicated auxiliary

SPS

 

power screw terminal

 

(configured in the

 

Programmer)

 

AUX POWER

 

 

0V 24V

TB3

 

 

0.75 mm2 to 4 mm2

Ferrite bead required for EMC compliance. Use SX0005 or kit 4100-5129.

Devices

Primary

Return

TB1

TB2

TB1

TB2

4090-91174090-9117

ISOLATOR 24VISOLATOR 0V

To SPS/

RPS

Class A aux power wiring requires the use of 4090-9117 IDNet Power Isolators, as shown above.

AUXILIARY

POWER

Maximum per NAC: 3 A

Maximum per Auxiliary Power output: 2 A

Class A wiring is possible only if 4090-9117 Power Isolators are used.

EMC compliant systems require ferrite beads. Use kit SX0005.

Figure 7-4. Auxiliary Power Wiring

7-9

Page 117
Image 117
Tyco 4100U installation manual SPS Auxiliary Power Wiring, Continued, 4.Auxiliary Power Wiring