Tyco 4100U installation manual SPS IDNet Wiring, Continued, 7.Class B Wiring

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 122
Image 122
Figure 7-7. Class B Wiring

SPS IDNet Wiring, Continued

Class B Wiring

To connect addressable devices/detectors to the SPS IDNet using Class B wiring, read the

 

following instructions.

 

1.

Under AS1670.1 Class B wiring is allowed only for a maximum of 40

 

 

addressable devices.

 

2.

A ferrite bead is required on the SPS IDNet cable.

 

3.

On TB1, jumper B+ to A+, and jumper B- to A-.

 

4.

Route wire (between 0.75 mm2 and 4 mm2) from the B+, B-.

The illustration below shows Class B wiring.

IDNet LINES TO DEVICES

(CLASS B / STYLE 4)

Ferrite bead required.

B+ B- SHLD A+ A-

IDNet

3

2P1

1

Figure 7-7. Class B Wiring

7-14

Page 122
Image 122
Tyco 4100U installation manual SPS IDNet Wiring, Continued, 7.Class B Wiring