Alignment & Adjustment

Alignment & Adjustment

Overview

All the 4100U cards and modules (pcbs) are tested and aligned in the factory before being

 

supplied to the customer or fitted to a FIP. The only field adjustment that may be

 

necessary is to set the battery charger voltage. (Note this has been set and should not

 

need re-adjusting).

 

R341

Battery Charger Voltage

 

Should the battery charger voltage need adjusting, the method is as follows:

 

1.

Run the system with the batteries connected and the door closed for at least 30

 

 

minutes to allow components to "warm up" (the longer the better).

 

2.

Calculate the required no-load battery charging voltage by taking 27.3V for

 

 

20°C and subtracting approximately 0.1V for every 3°C above 20°C, or adding

 

 

approximately 0.1V for every 3°C below 20°C.

 

3.

With the system not in Alarm, disconnect the batteries.

 

4.

Measure the voltage at the battery terminals and adjust to the voltage calculated

 

 

in Step 2 by turning pot R341.

 

5.

Re-connect the batteries.

11-3