Tyco 4100U Wiring Network Cards, Continued, 13.Fiber Optic, Style 7 Wiring, Notes

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 98
Image 98
Fiber Optic,

Step 4. Wiring Network Cards, Continued

Fiber Optic,

Style 7 Wiring

SEE NOTE 5

SEE NOTE 5

Notes:

SEE NOTE 5

1.Refer to general wiring precautions in this chapter, as well as Field Wiring Specifications: document 900-082 for 4100; 900-242 for 4100U. For specific information about fiber optic wiring, refer to the 900-143 Fiber Tutorial.

2.The maximum distance between nodes when using the fiber communication path is dependent upon the fiber’s multimode graded index: 10,000 feet (3,048 m) for 50/125 fiber; 15,000 feet (4,572 m) for 62.5/125 fiber. The maximum cable O.D. is 0.118 (3 mm). Reference document 900-143 for other fiber sizes.

3.ST connectors with long strain relief boots are to be used with the fiber optic cable.

4.On assembly 565-274, JW1 and JW2 must be installed. Jumper plugs must not be installed on P5-P8.

5.Cable clamps supplied with 748-531 are used to secure the fiber cable.

Figure 5-13. Fiber Optic, Style 7 Wiring

Continued on next page

5-18

Page 98
Image 98
Tyco 4100U Wiring Network Cards, Continued, 13.Fiber Optic, Style 7 Wiring, Continued on next page, Notes