Tyco installation manual Appendix H 4100U Specifications

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 174
Image 174
Appendix H

General

Fuses

Firmware Features

Appendix H

4100U Specifications

System Capacity

2,000 points of addressable points, plus 2,000 points of

annunciation. Expansion

Up to capacity above.

 

Up to 119 Addressable cards

Cabinet Size

Dependent on system configuration

Cabinet Material

1.6mm Zintex

Cabinet Finish

Powder coated

Cabinet Colour

Cream Wrinkle

Mounting

Wall mount

Mains Input

240V AC, +6%, -10%, 50Hz

Internal Power Supply

24V DC @ 9A

Standby Battery

24V sealed lead acid up 110Ah

Battery Charger

27.3V DC (nominal)

PSU Supervision

Charger high/low, Battery low/fail

Temperature

-5°C to 45°C

Humidity

10% to 90% RH non-condensing

Refer to Table 6-1, 6-2 for full SPS specifications.

Alarm Relay Card

F1 Alarm, 3A, 15 x 5mm, Glass Cartridge

F2 Supervisory, 3A, 15 x 5mm, Glass Cartridge

F3 Trouble, 3A, 15 x 5mm, Glass Cartridge

Fused Distribution Board (if fitted)

F1 24V Out, 1A 20 x 5mm Glass Cartridge

F2 24V Out, 1A 20 x 5mm Glass Cartridge

F3 24V Out, 1A 20 x 5mm Glass Cartridge

F4 24V Out, 1A 20 x 5mm Glass Cartridge

WALK TEST System Test

4 Operator Access Levels

Event Historical Logging

Device selectable Alarm Verification

Individual Zone Isolate

Addressable device disable/enable

Non-volatile Flash EPROM for field editable program changes

Expansion cards firmware upgraded via download to flash EPROMs

H-1

Page 174
Image 174
Tyco installation manual Appendix H 4100U Specifications