Tyco 4100U 1.TIC Specifications, Electrical Specifications, Environmental Specifications

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 74
Image 74
Table 5-1. TIC Specifications

Introduction to MINIPLEX Transponders (4100U), Continued

LEDs

Card Specifications

The TICs have the following LEDs:

LED1. Illuminates to indicate communication loss with the CPU.

LED2. Illuminates when an RUI ground fault search is active.

LED3. Illuminates when Local Mode is active.

LED4. Illuminates to indicate an RUI Style 7 primary trouble.

LED5. Illuminates to indicate an RUI Style 7 secondary trouble.

Refer to Figure 5-1 to see which LEDs are included on which TIC. Most TICs do not contain all LEDs.

Table 5-1 lists the specifications for all TICs.

Table 5-1. TIC Specifications

Electrical Specifications

Input Voltage

18-33 VDC

 

 

 

 

 

Output Voltage

8 V @ 1 A; 100 mV p-p ripple

 

 

 

 

 

Input Current

87 mA for all TICs. 112 mA for a local mode TIC

 

connected to a local mode annunciator.

 

 

 

 

 

 

 

 

Environmental Specifications

 

 

 

 

 

Operating

 

32° to 120° F (0° to 49° C)

 

Temperature

 

 

 

 

 

 

 

 

 

Humidity

 

10% to 93% relative humidity at 90° F (32° C)

 

 

 

 

 

 

 

 

 

4-6

Page 74
Image 74
Tyco 4100U installation manual 1.TIC Specifications, Electrical Specifications, Environmental Specifications