Tyco 4100U SPS IDNet Wiring, Continued, 6.Class A Wiring, Continued on next page

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 121
Image 121
SPS IDNet Wiring, Continued

SPS IDNet Wiring, Continued

Class A Wiring

To connect addressable devices/detectors to the SPS IDNet using Class A wiring, read the

 

following instructions.

 

1.

Ferrite beads are required on the SPS IDNet cables (ref Fig 7.1).

 

2.

Route wire (between 0.75 mm2 and 4 mm2) from the B+, B- outputs on TB1 of

 

 

the SPS to the appropriate inputs on a peripheral IDNet device.

 

3.

Route wire from the first IDNet device to the next one. Repeat for each device.

 

4.

Route wire from the last IDNet device to the A+ and A- inputs on TB1 of the

 

 

SPS.

IDNet

DEVICE

IDNet LOOP

(CLASS A / STYLE G)

IDNet

DEVICE

IDNet

DEVICE

Ferrite beads required.

 

 

 

 

3

P1

 

 

 

 

 

 

 

2

B+ B- SHLD A+ A-

1

 

 

 

 

 

 

 

 

 

 

IDNet

 

Figure 7-6. Class A Wiring

Continued on next page