Tyco 4100U Appendix A The Device Configuration DIP Switch, 1 2 3 4 5 6 7, Continued on next page

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 151
Image 151
Appendix A

Appendix A

The Device Configuration DIP Switch

Overview

Addressable cards include a bank of eight DIP switches. From left to right (see Figure A-

 

1, below) these switches are designated as SWx-1 through SWx-8. The function of these

 

switches is as follows:

 

SWx-1. This switch sets the baud rate for the internal 4100 communications line

 

running between the card and the CPU. Set this switch to ON.

 

SWx-2 through SWx-8. These switches set the card’s address within the 4100

 

FACP. Refer to Table A-1 for a complete list of the switch settings for all of the

 

possible card addresses.

 

Note: You must set these switches to the value assigned to the card by the

 

4100 Programmer.

4100 Comm. Baud Rate. Switch (SWx-1)

Must Be Set to ON

ON

OFF

DIP Switches SWx-2 through SWx-8 set the Card Address. Figure shows an Address of 3.

1 2 3 4 5 6 7 8

Figure A-1. DIP Switch SWx

Continued on next page

A-1

Page 151
Image 151
Tyco 4100U installation manual Appendix A The Device Configuration DIP Switch, 1 2 3 4 5 6 7, Figure A-1.DIP Switch SWx