Tyco 4100U installation manual Configuring the Card, 1 2 3 4 5 6 7, 4.DIP Switch SW1

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 128
Image 128
Configuring the Card

Configuring the Card

Overview

Setting the Shield Tie Point

Configuring the card consists of selecting the shield tie point, and setting the device address..

If a shielded cable is used, connect the cable shield to the dedicated terminal on TB1 and use jumper port (P1) to select where the shield will be tied.

Position 1 - 2 connects the shield to 0 V.

Position 2 - 3 connects the shield to Earth.

Setting the Address

The device address is set on DIP switch SW1, which is a bank of eight switches (see

 

figure below). From left to right, these switches are designated as SW1-1 through SW1-8.

 

The function of these switches is as follows:

 

SW1-1. This switch sets the baud rate for the internal 4100 communications

 

 

line running between the card and the 4100 CPU. Set this switch to ON.

 

SW1-2 through SW1-8. These switches set the card’s address within the

 

 

4100 FACP. Refer to the table in Appendix A for a complete list of the switch

 

 

settings for all of the possible card addresses.

 

Note:

You must set these switches to the value assigned to the card by the

 

 

4100 Programmer.

4100 Comm. Baud Rate. Switch (SW1-1)

Must Be Set to ON

ON

OFF

Dip Switches SW1-2 through SW1-8 set the Card Address. Figure shows an Address of 3.

1 2 3 4 5 6 7 8

Figure 8-4. DIP Switch SW1

8-6

Page 128
Image 128
Tyco 4100U installation manual Configuring the Card, 1 2 3 4 5 6 7, 4.DIP Switch SW1