Tyco installation manual Introduction to MINIPLEX Systems Non-4100U, Notes

Models: 4100U

1 180
Download 180 pages 17.54 Kb
Page 58
Image 58
Introduction to MINIPLEX Systems (Non-4100U)

Introduction to MINIPLEX Systems (Non-4100U)

Overview

The 4100 MINIPLEX Fire Alarm System uses transponder cabinets containing remote

 

interface cards (RICs) to extend power and communication across large areas.

 

MINIPLEX transponders allow the system to provide applications for up to 1000 monitor

 

and/or control points and 2000 annunciator points (see note). Using 4100-style serial

 

communications, up to 31 distributed MINIPLEX transponder locations are possible for

 

initiating device circuit cards, MAPNET II/

 

TrueAlarm addressable communications interfaces, notification appliance circuit cards,

 

LED/switch controls, auxiliary relay control cards, power supplies, and audio amplifiers.

 

By selecting the required combinations of modules and mounting MINIPLEX

 

transponders at the appropriate building locations, wire quantities are significantly

 

reduced for all monitor and control functions. Since power for the local modules is

 

provided from the local power supply, the wiring from the control panel need only be

 

separate twisted, shielded pairs for data, voice, and telephone.

 

Notes:

 

One point consists of one LED or one switch on an LED/switch module, one

 

LED driver output on a graphic driver, or one switch input on a graphic switch

 

input module.

 

Up to 32 modules can be controlled by one MINIPLEX transponder.

 

 

 

Continued on next page

3-30