(C12) ANC monitor switching ON/OFF setting
A N C M O N S E L E C T = O N
If there are 2 or more ANC inputs, set whether or not ANC inputs to be monitored are switched.
Setting Range
OFF (default), ON
(C13) Monitor switching control input terminal setting (When the ANC monitor switching is set to ON)
M O N S E L E C T C I N 0 1
Select the control input terminal to switch the ANC inputs* to be monitored.
Selecting the terminal overwrites the previously set function on it if there is.
Setting Range
CIN01 – 04, CIN01 – 12 when
Each time the designated terminal is closed, the ANC inputs to be monitored are switched in numerical order from ANC input 1.
*ANC inputs are the input channels of
(C14) Interlock output control setting (When the ANC monitor switching is set to ON)
M O N S E L S Y N C O N
Perform ON/OFF setting for the function that closes the control output terminal in synchronization with the control input terminal closure of the set number.
Setting Range
OFF (default), ON
(C15) Monitored ANC input channel selection
(When the ANC monitor switching is set to ON, and the interlock output control to ON)
S E L E C T S Y N C A N C 1
Select the ANC input channel. Each channel for which the monitor function is set to ON can be selected.
Setting Range
ANC 1 – 4 (Only ANC input channels for which the monitor function is ON)
(C16) Interlock output terminal setting
(When the ANC monitor switching is set to ON, and the interlock output control to ON)
S E L E C T S Y N C C O U T 0 1
Set the control output terminal which is closed in synchronization with switching to the monitored ANC input channel.
Assigning the function to this terminal overwrites the previously set function on it if there is.
Setting Range
COUT01 – 04, COUT01 – 12 when
59