3:USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE SOFTWARE OR
OPTIONAL SMART SLOT ACCESSORY CARDS. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.
FUNCTION | FACTORY | USER SELECTABLE |
| DESCRIPTION |
| |
DEFAULT | CHOICES |
|
| |||
|
|
|
| |||
Automatic | Every 14 days | Every 14 days | This function sets the interval at which the | |||
| (336 hours) | (336 hours), | uninterruptible power supply will execute a | |||
|
| Every 7 days |
|
| ||
|
| (168 hours), |
|
|
| |
|
| On Startup Only, |
|
|
| |
|
| No |
|
|
| |
|
|
|
| |||
UPS ID | UPS_IDEN | Up to eight characters | Use this field to uniquely identify the unin- | |||
|
|
| terruptible power supply, (i.e. server name | |||
|
|
| or location) for network management pur- | |||
|
|
| poses. |
|
| |
|
|
|
| |||
Date of Last Battery | Manufacture Date | mm/dd/yy | Reset this date when you replace the battery | |||
Replacement |
|
| module. |
|
| |
|
|
|
| |||
Minimum Capacity | 0 percent | 0, 15, 30, 45, 50, 60, 75, | The uninterruptible power supply will | |||
Before Return from |
| 90 percent | charge its batteries to the specified percent- | |||
Shutdown |
|
| age before it powers up connected equip- | |||
|
|
| ment, following a | |||
|
|
|
| |||
Alarm Control | Enable | Enable, Mute, Disable | User can mute an ongoing alarm or disable | |||
|
|
| all existing alarms permanently. | |||
|
|
|
| |||
Shutdown Delay | 90 seconds | 0, 90, 180, 270, 360, | The interval is set between the times when | |||
|
| 450, 540, 630 seconds | the uninterruptible power supply receives a | |||
|
|
| shutdown command and actual shutdown. | |||
|
|
|
| |||
Synchronized | 0 seconds | 0, 60, 120, 180, 240, | The uninterruptible power supply will wait | |||
Delay |
| 300, 360, 420 seconds | the specified time after the return of utility | |||
|
|
| power before | |||
|
|
| cuit overload). |
| ||
|
|
|
| |||
Output Voltage | 750THV, 1000THV | 750THV, 1000THV and | 750THV, 1000THV and 1500THV models: | |||
| and 1500THV mod- | 1500THV models: | Allows the user to select the output voltage. | |||
| els: | 220, 230, 240VAC |
|
|
| |
| 230VAC |
|
|
|
| |
|
|
|
| |||
Voltage Sensitivity | High | : Brightly illumi- | Adjust by pressing the voltage sensitivity | |||
The uninterruptible | button | (rear panel). Use a pointed ob- | ||||
| nated - high sensitivity. | |||||
power supply detects |
|
| ject (such as a pen) to do so. |
| ||
and reacts to line voltage |
| : Dimly illuminated | Note: In situations of poor power quality, | |||
distortions by transfer- |
| - medium sensitivity. | ||||
| the uninterruptible power supply may fre- | |||||
ring to battery operation |
|
| ||||
| : No illumination; | quently transfer to battery operation. If the | ||||
to protect connected |
| |||||
| connected equipment can operate normally | |||||
equipment. |
| low sensitivity. | ||||
| under such conditions, reduce the sensitivity | |||||
|
|
| ||||
|
|
| setting to conserve battery capacity and | |||
|
|
| service life. |
|
| |
|
|
|
| |||
Low Battery Warning |
|
| The uninterruptible power supply will beep | |||
| 2 minutes | : Brightly illumi- | when two minutes of battery runtime re- | |||
| PowerChute software | nated - low battery | mains. |
|
| |
| warning level of about | Change the warning interval setting by | ||||
| provides automatic, | |||||
| two minutes. | |||||
| unattended shutdown | pressing the voltage sensitivity button, while | ||||
|
| |||||
| when approximately | : Dimly illuminated | pressing and holding the | button. | ||
| two minutes of bat- | |||||
| tery operated runtime | - low battery warning | Change the low battery warning interval | |||
| level of about five min- | |||||
| remains. | |||||
| utes. | setting to the time that the operating system | ||||
|
| |||||
|
|
| or system software requires to safely shut | |||
|
| : No illumination; | down. |
|
| |
|
| low battery warning |
|
|
| |
|
| level is approximately |
|
|
| |
|
| eight minutes. |
|
|
| |
|
| Possible interval set- |
|
|
| |
|
| tings: 2, 5, 8, 11, 14, 17, |
|
|
| |
|
| 20, 23 minutes. |
|
|
| |
|
|
|
|
|
|
9