NOTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE SOFTWARE OR
OPTIONAL SMART SLOT ACCESSORY CARDS. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
High Transfer Point | 750TLV, 1000TLV | 750TLV, 1000TLV | If the utility voltage is usually high and the | |
| and 1500TLV mod- | and 1500TLV models: | connected equipment is specified to operate | |
| els:127AC | 127, 130, 133, 136VAC | with input voltages this high, set the high | |
| 750THV, 1000THV | 750THV, 1000THV | transfer point higher to avoid unnecessary | |
| battery usage. | |||
| and 1500THV mod- | and 1500THV models: |
| |
| els:253VAC | 253, 257, 261, 265VAC |
| |
|
|
|
| |
Low Transfer Point | 750TLV, 1000TLV | 750TLV, 1000TLV | If the utility voltage is usually low and the | |
| and 1500TLV mod- | and 1500TLV models: | connected equipment is specified to operate | |
| els:106VAC | 97, 100, 103, 106VAC | with input voltages this low, set the low | |
| 750THV, 1000THV | 750THV, 1000THV | transfer point lower. | |
|
| |||
| and 1500THV mod- | and 1500THV models: |
| |
| els:208VAC | 196, 200, 204, 208VAC |
| |
|
|
|
|
10