PROBLEM AND/OR POSSIBLE |
| SOLUTION |
CAUSE |
|
|
THE REPLACE BATTERY LED IS ILLUMINATED | ||
Replace battery LED flashes |
| Check that the battery connectors are fully engaged. |
and short beep is emitted every |
|
|
two seconds to indicate the |
|
|
battery is disconnected. |
|
|
|
|
|
Weak battery. |
| Allow the battery to recharge for 24 hours. Then, perform a |
|
| problem persists after recharging, replace the battery. |
|
|
|
Failure of a battery |
| The uninterruptible power supply emits short beeps for one minute and the |
|
| replace battery LED illuminates. The uninterruptible power supply repeats |
|
| the alarm every five hours. Perform the |
|
| has charged for 24 hours to confirm the replace battery condition. The |
|
| alarm stops and the LED clears if the battery passes the |
|
| |
THE SITE WIRING FAULT LED ON THE REAR PANEL IS ILLUMINATED (750TLV, 1000TLV & 1500TLV | ||
MODELS ONLY) |
|
|
The uninterruptible power sup- |
| Wiring faults detected include missing ground, |
ply is plugged into an improp- |
| and overloaded neutral circuit. |
erly wired utility power outlet. |
| Contact a qualified electrician to correct the building wiring. |
|
| |
|
| |
THE INPUT CIRCUIT BREAKER HAS TRIPPED | ||
The plunger on the circuit |
| Reduce the load on the uninterruptible power supply by unplugging equip- |
breaker pops out. |
| ment. Press in the plunger on the circuit breaker. |
|
| |
THE AVR BOOST OR TRIM LEDS ARE ILLUMINATED | ||
Your system is experiencing |
| Have qualified service personnel check your facility for electrical prob- |
excessive periods of low or |
| lems. If the problem continues, contact the utility company for further as- |
high voltage. |
| sistance. |
|
| |
UNINTERRUPTIBLE POWER SUPPLY OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE | ||
EXISTS |
|
|
The uninterruptible power |
| To reduce the load on the uninterruptible power supply, unplug equipment |
supply input circuit breaker |
| and press in the plunger on the circuit breaker. |
tripped. |
|
|
|
|
|
Very high, low, or distorted |
| Move the uninterruptible power supply to a different outlet on a different |
line voltage. |
| circuit, as inexpensive fuel powered generators may distort the voltage. Test |
|
| the input voltage with the utility voltage display (see Operation). If accept- |
|
| able to the connected equipment, reduce the uninterruptible power supply |
|
| sensitivity. |
|
| |
BATTERY CHARGE AND BATTERY LOAD LEDS FLASH SIMULTANEOUSLY | ||
The uninterruptible power |
| Check that the room temperature is within the specified limits for operation. |
supply has shutdown. The |
| Check that the uninterruptible power supply is properly installed, allowing |
internal temperature of the |
| |
| for adequate ventilation. | |
uninterruptible power supply |
| |
|
| |
has exceeded the allowable |
| Allow the uninterruptible power supply to cool down. Restart the uninter- |
threshold for safe operation. |
| ruptible power supply. If the problem continues, contact IBM. |
|
|
|