Basic Operation continued
Power Sensitivity Adjustment: This dial is normally set fully counter- clockwise, which enables the UPS to provide maximum protection against waveform distortions in its AC input. When such distortion occurs, the UPS will normally switch to providing sine wave power from its battery reserves for as long as the distortion is present. In areas with poor utility power or where the UPS’s input power comes from a backup generator, chronic waveform distortion could cause the UPS to switch to battery too frequently, draining its battery reserves. You may be able to reduce how often your UPS switches to battery due to moderate waveform distortion by experimenting with different settings for this dial. As the dial is turned clockwise, the UPS becomes more tolerant of variations in its input power’s AC waveform.
Note: The further the dial is adjusted clockwise, the greater the degree of waveform distortion the UPS will allow to pass to connected equipment. When experimenting with different settings for this dial, operate connected equipment in a safe test mode so that the effect on the equipment of any waveform distortions in the UPS’s output can be evaluated without disrupting critical operations.
Input Breakers: The SMART2500XLHG uses two input breakers to protect your electrical circuit from overcurrent draw from the UPS load. One breaker protects LINE, while the other NEUTRAL. If these breakers trip, remove some of the load and reset them by pressing the breakers in.
Guidance and Manufacturer’s Declaration
Product Information
AC Input Voltage | 120V |
Input Amp(s) | 16A |
No. of Phases | Single |
Class Type | Class 1 |
Plug/Connector Type | IEC inlet C20 |
|
|
Operation | Continuous |
|
|
AC Input Frequency | 60Hz |
AC Input Protection (Qty./Type/Rating) | Input breaker (2x 20A thermal) |
Max AC Leakage Current (uA) | Less than 100uA |
Weight | 73.3 lbs (33.2 kg) |
|
|
Contraindication | None |
|
|
Guidance and Manufacturer’s
This
Emissions Test | Compliance | Electromagnetic Environment - Guidance |
RF Emissions CISPR 11 | Group 1 | The |
|
| function. Therefore, its RF emissions are very low and unlikely |
|
| to cause any interference in nearby electronic equipment. |
RF Emissions CISPR 11 | Class B | The |
|
| establishments other than domestic and those directly |
|
| connected to the public |
|
| that supplies buildings used for domestic purposes. |
|
|
|
10