System Configuration | Section | |
|
|
|
There are three models of Expansion Units available: the Analog I/O Unit, Com- poBus/S I/O Link Unit, and Temperature Sensor Units.
Expansion Connector
Expansion I/O Unit, Analog I/O Unit, CompoBus/S I/O Link Unit, or Tem- perature Sensor Unit)
Expansion I/O Connecting Cable
A PC with 100 I/O points (the maximum) can be assembled by connecting three
Expansion I/O Units.
⋅ 1 Unit | + | ⋅ 3 Units = 60 inputs, 40 outputs | ||
(24 inputs, 16 outputs) | (12 inputs, 8 outputs) |
A PC with 6 analog inputs and 3 analog outputs (the maximum) can be as- sembled by connecting three Analog I/O Units.
A PC with up to 6 temperature inputs for input from thermocouples or platinum resistance thermometers can be assembled by connecting Temperature Sensor Units.
CompoBus/S I/O Link Units (Slave Units) can be connected to a CPU Unit. I/O data (8 inputs and 8 outputs) is transferred between the CPU Unit and the area allocated to the CompoBus/S Slave. (The I/O data exchanged with the Slave is internal data; there are no external input or output terminals.)
Note Different types of Expansion Units can be connected at the same time. For ex- ample, an Expansion I/O Unit, Analog I/O Unit, and CompoBus/S I/O Link Unit, or an Expansion I/O Unit, Analog I/O Unit, and Temperature Sensor Unit can be connected to the CPU Unit.
Expansion I/O Units
Unit | Max. number | Inputs | Outputs | Model | |
| of Units |
|
|
| |
|
|
|
|
| |
20 I/O points | 3 Units max. | 24 VDC | Relays | ||
| (See note.) |
|
|
| |
12 inputs | 24 VDC | Sinking transistors | |||
| |||||
8 outputs |
| 24 VDC | Sourcing transistors | ||
|
| ||||
|
|
|
|
| |
8 inputs |
| 24 VDC | |||
|
|
|
|
| |
8 outputs |
| Relays | |||
|
|
|
|
| |
|
| Sinking Transistors | |||
|
|
|
|
| |
|
| Sourcing Transistors |