Programming Console Operations | Section | |
|
|
|
2.Press the SET Key to force the bit ON or press the RESET Key to force the bit OFF.
| 0000020000 |
SET | ON^ ON |
|
The cursor in the lower left corner of the display indicates that the force set/ reset is in progress. Bit status will remain ON or OFF only as long as the key is held down; the original status will return one cycle after the key is released.
3.Press the SHIFT and SET Keys or SHIFT and RESET Keys to maintain the status of the bit after the key is released. In this case, the
To return the bit to its original status, press the NOT Key or perform the Clear Force Set/Reset operation. Refer to
Forced status will also be cleared in the following cases:
a)When the PC’s operating mode is changed (although the forced status will not be cleared when the mode is changed between PROGRAM and MONITOR if SR 25211 is ON)
b)When the PC stops because a fatal error occurred
c)When the PC stops because of a power interruption
d)When the Clear Force Set/Reset Operation is performed
4-3-24 Clear Force Set/Reset
This operation is used to restore the status of all bits which have been force set or reset. It is possible in MONITOR or PROGRAM mode only.
RUN | MONITOR | PROGRAM |
|
|
|
No | OK | OK |
!Caution Before changing the contents of I/O memory, be sure that the changes will not cause equipment to operate unexpectedly or dangerously. In particular, take care when changing the status of output bits. The PC continues to refresh I/O bits even if the PC is in PROGRAM mode, so devices connected to output points on the CPU Unit or Expansion I/O Units may operate unexpectedly.
1, 2, 3... 1. Press the CLR Key to bring up the initial display.
2.Press the SET and then the RESET Key. A confirmation message will appear.
00000FORCE RELE?
SET RESET
Note If you mistakenly press the wrong key, press CLR and start again from the beginning.
3. Press the NOT Key to clear the
00000FORCE RELE
NOT END
4-3-25 Hex-ASCII Display Change
This operation is used to convert word data displays back and forth between
The displayed PV of the timer or counter cannot be changed.
RUN | MONITOR | PROGRAM |
|
|
|
OK | OK | OK |
100