MGE UPS Systems EX-5, EX-7, EX-11RT manual System Electrical Characteristics

Page 17

Installation and User Manual

1.1System Electrical Characteristics

Table 1-3: UPS Characteristics System Ratings.

 

 

 

 

 

 

 

 

UPS Characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAIN 1 (Normal AC Source) default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

Input Current (A)

 

 

Input

 

Output

Output

 

 

 

Power

 

 

 

 

 

 

 

 

 

 

 

Inrush

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

Breaker

 

Voltage

Current

 

Rating

 

Min

Max

 

Online

 

Bypass

 

 

Current

 

 

(VAC)

 

 

 

 

 

 

 

 

 

(A)

 

(VAC)

(A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 kVA

 

 

18

 

32

 

21.6

 

19

40

 

 

 

19.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7 kVA

208

 

25

 

45

 

30.3

 

26.65

50

 

208

23.5

 

200A/1ms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11 kVA

 

 

38

 

64

 

44

 

42

70

 

 

 

47.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1-4: Transformer Module Characteristics Ratings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transformer Module Characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Voltage (VAC)

 

 

 

 

 

 

 

 

208/240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Voltage (VAC)

 

 

 

120/120

 

 

 

208

 

 

 

240

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. Output Current (A)

 

 

33.3/33.3

 

 

 

52

 

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

Power Module is factory configured at 208Vac, 60 Hz input and output.

 

 

 

 

 

 

 

 

 

Without transformer, Input and Output of the UPS must always be

 

 

 

 

 

 

 

 

the same.

 

 

 

 

 

 

 

 

 

 

 

 

 

On 11KVA, 10% de-rating for 200/208VAC. Isolated 120/208/240VAC are available with EX RT Transformer Module.

86-86000-00 B00

Introduction

1 — 3

Image 17
Contents EX 5/7/11RT Systems Page Technical Support Customer Care Center Hours 24/7 MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714EX 5/7/11RT Systems Contents Setup and Installation Return Policy for Repair of Single Phase Products RGA Technical Support and Product ServicesFigures Tables Certification Standards Important Safety InstructionsEnvironment Special PrecautionsAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Input voltage must be the same as output voltage on HV units ScopePart Number Description Transformer Module Characteristics Ratings System Electrical CharacteristicsTower Configuration Standard ConfigurationRack Configuration Model Dimensions HxWxD WeightsRear Panel Components Power Module EX 5/7/11 RT1 1 R T Power Module Display and Control PanelEX RT Transformer Module Battery/Transformer/CLA Module Rail Kit Optional AccessoriesPower Module Rail Kit Battery Extension Cable Kit Multiple Battery Module Backup Time at Full LoadInput/Output Box Battery Integration Kit with CastersEX RT Transformer Module Contents Recommended Batteries CLA Module ContentsEX 5/7/11RT All Modules are shipped in separate boxes Unpacking and Parts CheckContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Bracket System Install input/output cables Per .7 prior to this stepCommunication Ports Connecting the RS232 Communication PortInstallation of Optional Transverse Card Connecting the Dry Relay Contact Communication PortJBus Card Dual U-Talk/Basic CardProper operation Dual port Shut CardRemote Emergency Power Off Repo Communication Port Sources are open OFF/OPEN System ConnectionsMax AWG EX 11RT Output Always connect the earth ground wire first120VAC output terminals Lb-N, La-N Connecting EX RT Transformer ModuleProtection for all transformer output terminals Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB Connection of Optional CLA Module AC InputThis page left blank intentionally Required for initial startup only Initial StartupControl Panel with scroll up and down buttons UPS PersonalizationDisplay Factory setting Options Comments Display Factory setting OptionsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode UPS personalization through external software Then go to Advanced settings and UPS settingsFinal Startup sequence During the startup, if the Bypass AC source is outOperating Modes Normal double conversion ModeECO mode display ECO ModeTransfer to Battery Power Operation on Battery PowerFirst Case Operation on battery Second Case Low battery warningShutdown Power to the loadReturn of Normal AC source Symptoms Indication Correction TroubleshootingBattery Fault LED 1CXXXXXXX Hot Swapping the Power ModuleRe-connecting the Power Module Re-connecting the Battery Module Hot Swapping the Battery ModuleDisconnecting the Battery Module This page left blank intentionally System Input/Output Power Ratings Electrical SpecificationsSystem Overload Characteristics Source Voltage FrequencyEX RT CLA Module System Backup CharacteristicsSystem Short Circuit Protection KVA / kW 25% 50% 75% 100% Output load percentage Configuration for Hours backup timeOperation Mode On-line On Battery Environmental CharacteristicsHeat Rejection SystemProprietary Rights Statement MGE Standard Single Phrase WarrantyProduct information Warranty Extension Warranty+ not available on productsUser Information Part Number Assembly Number Serial number Scheduling Field Service Engineer SupportEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE