MGE UPS Systems EX-5, EX-7, EX-11RT manual System Backup Characteristics, EX RT CLA Module

Page 64

EX 5/7/11RT Systems

5.3System Backup Characteristics

Table 5-2: Backup Time (in minutes).

11 kVA with 9Ah battery modules:

 

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Standard

90

40

25

18

14

11

9

7

6

5

Std + 1 EXB

191

93

61

43

30

24

20

17

15

14

Std + 2 EXB

293

143

96

71

53

44

34

27

24

22

Std + 3 EXB

392

199

135

99

84

60

51

43

35

30

Std + 4 EXB

525

261

172

120

102

86

67

56

48

42

Std + 5 EXB

637

312

201

142

113

102

87

68

60

53

7 kVA with 7Ah battery modules:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Standard

121

57

37

28

21

15

12

10

8

7

Std + 1 EXB

266

125

80

61

53

37

30

24

22

20

Std + 2 EXB

447

203

124

101

83

66

55

45

38

32

Std + 3 EXB

578

244

185

128

108

90

75

61

53

45

Std + 4 EXB

756

364

245

169

132

110

98

77

69

57

Std + 5 EXB

889

453

287

232

164

133

118

102

86

72

5 kVA (US model only) with 7Ah battery modules:

 

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

Standard

170

91

49

33

25

21

16

13

11

9

Std + 1 EXB

358

170

110

84

60

46

39

31

27

25

Std + 2 EXB

540

260

170

120

100

75

64

57

52

45

Std + 3 EXB

740

355

240

170

122

110

95

84

68

60

Std + 4 EXB

892

505

290

235

170

135

119

105

92

84

Std + 5 EXB

1220

540

355

260

225

170

140

120

110

100

5.4System Short Circuit Protection

Short circuit current provided by EX 5/7/11RT in normal or battery mode:

EX 5/7RT

110A for 80ms

EX 11RT

150A for 80ms

5.5Accessories Electrical Characteristics

EX RT Transformer Module

Nominal power

11 kVA

Nominal current

63 A

Input voltage

208-240Vac

Output Voltage

120/208/240Vac

Frequency

50/60 Hz (+/-10%)

Isolation (EN 61558-1-2-4)

3.75 kV / 5 M ohms

Operating temperature

From 0° to +40°C

Max. operating rel. humidity

95%

Derating/altitude

Pn-10% > 1000 m

EX RT CLA Module

AC input voltage

156-280 Volts AC

Input frequency

40-70 Hz

Battery charge current

6 A DC

5 — 2

Appendix

86-86000-00 B00

Image 64
Contents EX 5/7/11RT Systems Page MGE UPS SYSTEMS, INC Scenic Avenue Costa Mesa, CA 92626 714 Technical Support Customer Care Center Hours 24/7EX 5/7/11RT Systems Contents Setup and Installation Technical Support and Product Services Return Policy for Repair of Single Phase Products RGAFigures Tables Important Safety Instructions Certification StandardsSpecial Precautions EnvironmentAdditional Modules Serial Numbers Section Descriptions This page left blank intentionally Scope Input voltage must be the same as output voltage on HV unitsPart Number Description System Electrical Characteristics Transformer Module Characteristics RatingsStandard Configuration Tower ConfigurationModel Dimensions HxWxD Weights Rack ConfigurationPower Module EX 5/7/11 RT Rear Panel ComponentsEX RT Transformer Module Power Module Display and Control Panel1 1 R T Power Module Rail Kit Optional AccessoriesBattery/Transformer/CLA Module Rail Kit Multiple Battery Module Backup Time at Full Load Battery Extension Cable KitBattery Integration Kit with Casters Input/Output BoxEX RT Transformer Module Contents EX 5/7/11RT CLA Module ContentsRecommended Batteries Unpacking and Parts Check All Modules are shipped in separate boxesContents of Standard EX 5/7/11RT Systems Contents of EXB 5/7/11RT Battery Module PN 86207 /86209 Installation in Tower Configuration Installation in Rack Mounting Configuration Not to scale Page Install input/output cables Per .7 prior to this step Bracket SystemConnecting the RS232 Communication Port Communication PortsConnecting the Dry Relay Contact Communication Port Installation of Optional Transverse CardDual U-Talk/Basic Card JBus CardProper operation Dual port Shut CardRemote Emergency Power Off Repo Communication Port Max AWG EX 11RT System ConnectionsSources are open OFF/OPEN Always connect the earth ground wire first OutputProtection for all transformer output terminals Connecting EX RT Transformer Module120VAC output terminals Lb-N, La-N Bypass AC Mains Power Module I/O Box Connection of Battery Module EXB AC Input Connection of Optional CLA ModuleThis page left blank intentionally Initial Startup Required for initial startup onlyUPS Personalization Control Panel with scroll up and down buttonsDisplay Factory setting Options Display Factory setting Options CommentsMGE UPS SYSTEMS, INC Symptoms IT Network mode Industrial mode Then go to Advanced settings and UPS settings UPS personalization through external softwareFinal Startup sequence During the startup, if the Bypass AC source is outNormal double conversion Mode Operating ModesECO Mode ECO mode displayOperation on Battery Power Transfer to Battery PowerFirst Case Operation on battery Second Case Low battery warningReturn of Normal AC source Power to the loadShutdown Troubleshooting Symptoms Indication CorrectionBattery Fault LED Hot Swapping the Power Module 1CXXXXXXXRe-connecting the Power Module Disconnecting the Battery Module Hot Swapping the Battery ModuleRe-connecting the Battery Module This page left blank intentionally Electrical Specifications System Input/Output Power RatingsSystem Overload Characteristics Source Voltage FrequencySystem Short Circuit Protection System Backup CharacteristicsEX RT CLA Module Configuration for Hours backup time KVA / kW 25% 50% 75% 100% Output load percentageEnvironmental Characteristics Operation Mode On-line On BatteryHeat Rejection SystemMGE Standard Single Phrase Warranty Proprietary Rights StatementUser Information Warranty Extension Warranty+ not available on productsProduct information Scheduling Field Service Engineer Support Part Number Assembly Number Serial numberEX 5/7/11RT Systems Glossary IEC Osha This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Contact MGE